![](/images/new-backgrounds/1010323/1032315x1.webp)
3. Combustion | & Ventilation | Air |
|
For Single Pipe | Installation | Air Openings and Connecting | Ducts |
|
| Total input rating for all non direct vent gas appliances | |
|
| MUST be considered when determining free area of open- | |
CARBON MONOXIDE POISONING HAZARD | ings. |
| |
|
| ||
|
| 2, Connect ducts or openings directly | to outside. |
Failure to provide adequate combustion and
ventilation air could result in death and/or personal injury.
Use methods described here to provide combustion
and ventilation air.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open- ings for supplying combustion and ventilation air must comply with
National Fuel Gas Code, NFPA54/ANSI Z223.1, 2002 (or current edition) and applicable provisions of local building codes.
This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a facto- ry- built or masonry chimney. If this furnace is replacing a previous-
ly
other remaining appliance(s). See "Venting and Combustion Air Check"in this section, This furnace MUST be vented to the out- side.
3.When screens are used to cover openings, they MUST be no less than 1/4" mesh.
The minimum dimension of rectangular air ducts MUST NOT be less than 3".
5.When sizing grille or louver, use the free area of opening. If
free area is NOT stamped or marked on grill or louver, as- sume a 20% free area for wood and 60% for metal.
Confined Space Installation
NOTE: A confined space is defined as an area with less than 50
cubic feet per 1,000 BTUH input rating for all gas appliances installed in the area.
Requirements
Provide confined space with sufficient air for proper com- bustion and ventilation of flue gases using horizontal or ver- tical ducts or openings.
Figure 5 illustrate how to provide combustion and ventila- tion air. A minimum of two permanent openings, one inlet and one outlet, are required.
|
|
|
| Outside | Air (This | is ONLY | a |
| guide. | Subject | to | codes of | country | having | jurisdiction.) |
| |||||||
|
|
|
| CableVent This | installation | NOT | approved | in Canada |
|
|
| GasVen_. |
|
|
| ||||||||
| Gas Vent |
|
|
|
| .J |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| x. |
| c,,en |
|
| .... |
|
| ,dNI |
| a___aOut,et | |||||
|
| Outlet Air (1)')I I |
| Soffit | Vent | _ / |
| .ir(1)I JL__q3. | II | II | |||||||||||||
|
|
|
| II |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 11I |
| II II | ||
|
|
|
| I | I |
|
|
| ]- |
|
| OutletAir'l'_] | I SoffitVent | In.let | _4........I I_;:;:,1 | ___.L_U, tnlet | |||||||
|
| I | I | A | _ |
|
|
|
| _ |
| _ | I |
| II | I | MinimumOnelnletandOneOutletAirSupplyisRequired | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| I |
| II | I | May | bein | any Combination | Shown |
|
| |
|
|
|
|
|
|
|
|
| Inlet | _ | ,r_o, | I | _"_1 |
| I I | I | Inlet | Air | Opening Must be Within12" | of floor |
| ||
|
| alternate | lnlet Air | (1) |
|
| AIr(l) | _ |
|
| Iq | [_:_"r_r | _ilrei2 ) | OutletAirOpeningMustbeWithinl2"ofceiling |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (1)1SquareInchper4000BTUH |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
3. | One | opening | MUST |
| be | within | 12" of the | floor and the sec- | 5. | Horizontal | duct openings require I square | inch of free area | |||||||||||
| ond | opening | within | 12" | of the | ceiling. |
|
|
|
|
|
|
| per 2,000 | BTUH of combined | input for all gas appliances in | |||||||
4. | Size | openings |
| and | ducts | per | Table | 1. |
|
|
|
|
|
|
| area (see Table 1). |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6.Vertical duct openings or openings directly to outside re- quire 1 square inch of free area per 4,000 BTUH for com- bined input of all gas appliances in area (see Table 1).
E_ | 440 01 1020 04 |