Siemens L-828CCRs LC-Type4, 7.5, and 10 kW/6.6 A/60 Hz, Installation, 6Input/Output Wiring

Models: L-828

1 64
Download 64 pages 48.3 Kb
Page 28
Image 28
Figure 3-6 Input/Output Wiring

L-828 CCRs LC-Type (4, 7.5, and 10 kW/6.6 A/60 Hz)

Installation

Wiring Connections and

Startup (contd.)

Figure 3-6 Input/Output Wiring

2.See Figure 2-4. Verify that the input supply voltage corresponds to the voltage rating on the name plate (8) of the regulator.

3.Make sure the rotary switch S1 (6) on the front panel is set to the OFF position.

4.Ground the regulator by making an adequate ground wire (AWG 6 or larger) connection to the earth ground lug (9) on the regulator.

NOTE: An appropriate disconnect-type fuse cutout or circuit breaker shall be provided for the input power supply lines. For installations requiring load switching during regulator operation, the regulator may be connected to an L-847 circuit selector switch.

NOTE: Do not use the LC-Type CCR to power an L-849 REIL system unless the CCR is at least half loaded with steady burning lights.

2002 Siemens Airfield Solutions, Incorporated

96A0104B

Page 3-6

All rights reserved

Issued 6/02

 

Page 28
Image 28
Siemens manual L-828CCRs LC-Type4, 7.5, and 10 kW/6.6 A/60 Hz, Installation, Wiring Connections and Startup contd