Siemens General Troubleshooting, Procedures, L-828CCRs LC-Type4, 7.5, and 10 kW/6.6 A/60 Hz

Models: L-828

1 64
Download 64 pages 48.3 Kb
Page 44
Image 44
3. General Troubleshooting

L-828 CCRs LC-Type (4, 7.5, and 10 kW/6.6 A/60 Hz)

Troubleshooting

 

 

 

This subsection provides general troubleshooting procedures.

 

3. General Troubleshooting

 

Procedures

 

 

 

 

 

 

 

 

 

 

 

 

 

Problem

 

 

Possible Cause

Corrective Action

 

 

1. Regulator not

Circuit breaker tripped

Turn off CCR using local control switch

 

 

turning on using

 

 

 

S1. Then turn on the CCR. Verify that

 

 

switch S1

 

 

 

nothing happens and that green LED

 

 

 

 

 

 

labeled REGULATOR ON is unlit. If these

 

 

 

 

 

 

conditions hold, then the circuit breaker

 

 

 

 

 

 

CB1 is tripped. Reset CB1 by switching on

 

 

 

 

 

 

breaker. If CB1 trips again, check and

 

 

 

 

 

 

replace fuses F1 and F2.

 

 

 

 

 

 

Use an AC voltmeter to probe signals.

 

 

 

 

 

 

Connect black lead on meter (common)

 

 

 

 

 

 

to earth ground lug on CCR.

 

 

 

 

 

 

Probe J3 terminals 4 and 6. Each should

 

 

 

 

 

 

read approximately 60 Vac. If they don’t

 

 

 

 

 

 

read 60 Vac, replace transformer T3.

 

 

 

 

 

 

Use an AC voltmeter to probe J3

 

 

 

 

 

 

terminals 1 and 3. Each should read

 

 

 

 

 

 

approximately 18 Vac. If they don’t read

 

 

 

 

 

 

18 Vac, replace transformer T4.

 

 

 

Control PCB

 

If J3 terminals 1 and 3 have normal

 

 

 

 

 

 

readings, the replace Control PCB, ribbon

 

 

 

 

 

 

cable, or Switch PCB, in that order.

 

 

2. Regulator does not

TB2 signals not working

Test signals to remote control TB2. If TB2

 

 

turn on using

 

 

 

signals do not work, repair external

 

 

remote control but

 

 

 

remote control switch or wiring.

 

 

operates using local

 

 

 

 

 

 

control switch S1

CCI wiring not connected to TB2

Check CCR wiring and replace fuse F3 on

 

 

 

 

 

 

terminal 8 for 120 Vac remote

the panel with a new ¼-amp slow-blow

 

 

 

control signal

fuse.

 

 

 

LEDs for 5-Step CCR or LEDs 1 and 3

Replace PCB.

 

 

 

for a 3-Step not lit

 

 

 

 

 

 

 

Check SCRs and wiring.

 

 

 

 

 

 

Replace SCR.

 

 

 

 

 

 

Continued on next page

 

2002 Siemens Airfield Solutions, Incorporated

96A0104B

Page 6-3

All rights reserved

Issued 6/02

 