Siemens L-828 manual Input Power Breaker Sizing, Specifications, Ratings, Class, Description

Models: L-828

1 64
Download 64 pages 48.3 Kb
Page 18
Image 18
6.Input Power Breaker Sizing

L-828 CCRs LC-Type (4, 7.5, and 10 kW/6.6 A/60 Hz)

Description

6.60 Hz LC-Type L-828 CCRs (4-10 kW/6.6 A): Required Equipment (contd.)

NOTE: Table 2-4 refers to recommended input power supply wire, less than 100 feet, 90°C, 600 or 5000 V minimum. For 100 to 250 feet, use the next larger (even) gage wire.

Table 2-4 Recommended Input Wiring Rating

kW Rating

208 Vac

220 Vac

240 Vac

480 Vac

 

 

 

 

 

4 kW

AWG 12, 600 V

AWG 12, 600 V

AWG 12, 600 V

AWG 16, 600 V

7.5 kW

AWG 8, 600 V

AWG 8, 600 V

AWG 10, 600 V

AWG 14, 600 V

10 kW

AWG 6, 600 V

AWG 6, 600 V

AWG 6, 600 V

AWG 12, 600 V

Table 2-5 Optional Lightning Arrestors

Input Voltage

Lightning Arrestor Part Number

208/220/240 Vac

94B0011-2

480 Vac

94B0011-1

6.Input Power Breaker Sizing

It is recommended that the circuit breaker on the input power supply lines have a rating of 125% of the CCR’s input current, as given in Table 2-5, unless local codes require a different rating technique. Refer to the CCR’s nameplate for the kW rating and input voltage to determine the actual input current from Table 2-5. If no standard- size circuit breaker exists at the 125% value, use the next larger standard-size circuit breaker.

NOTE: The currents listed in Table 2-6 represent actual input currents assuming the worst case limits of AC 150/5345-10E for power factor, efficiency, and number of required lamps out.

Table 2-6 CCR Input Current

 

Rating

208 Vac

 

220 Vac

240 Vac

 

480 Vac

 

4 kVA

27 A

 

26 A

24 A

 

12 A

 

7.5 kVA

51 A

 

48 A

44 A

 

22 A

 

10 kVA

68 A

 

65 A

59 A

 

30 A

 

 

 

This subsection provides specifications for L-828 CCR

 

7. Specifications

 

 

 

 

 

 

 

(4-10 kW/6.6 A).

 

 

 

 

 

 

 

 

 

 

Ratings

 

 

4, 7.5, 10 kW

 

 

 

Class

 

 

Class 1, 6.6 A (maximum output current)

 

2002 Siemens Airfield Solutions, Incorporated

96A0104B

Page 2-6

All rights reserved

Issued 6/02

 

Page 18
Image 18
Siemens Input Power Breaker Sizing, Specifications, Ratings, Class, L-828CCRs LC-Type4, 7.5, and 10 kW/6.6 A/60 Hz