Siemens manual L-828CCRs LC-Type4, 7.5, and 10 kW/6.6 A/60 Hz, Troubleshooting, Problem

Models: L-828

1 64
Download 64 pages 48.3 Kb
Page 47
Image 47
LED light lit (contd.)

L-828 CCRs LC-Type (4, 7.5, and 10 kW/6.6 A/60 Hz)

Troubleshooting

4.General Troubleshooting Procedures (contd.)

Problem

Possible Cause

Corrective Action

7. W VA-Indicator red

CCR’s output current not properly

Refer to calibration instruction in

LED light lit (contd.)

calibrated

Calibrating Regulators in the Installation

 

 

section.

 

TB5 wired to wrong voltage

See wiring diagram in Figure 8-1 in the

 

 

Wiring Schematics section. If 480 V

 

 

connection has been made for 208-240 V

 

 

CCR input, or vice versa, contract the

 

 

Siemens Airfield Solutions Sales

 

 

Department. Refer to warning below.

 

WARNING: A CCR wired for 480 Vac must not be changed to

 

240, 220, or 208 Vac. A CCR wired for 240, 220, or 208 must

 

not be changed to 480 Vac. Failure to observe this warning

 

may result in equipment damage.

2002 Siemens Airfield Solutions, Incorporated

96A0104B

Page 6-6

All rights reserved

Issued 6/02

 