SPX Cooling Technologies Marley MD specifications 1.5m from air

Models: Marley MD

1 40
Download 40 pages 61.95 Kb
Page 13
Image 13
Manual background

Marley / MD CoolingTower / Engineering Data : Schematic

13

 

 

 

 

 

 

 

 

MD5010 MULTICELL

 

 

 

 

 

 

 

 

 

 

 

 

 

dBA

 

Dimensions

Design

Shipping Weight

Model

Nominal Tons

Motor

 

Operating

 

kg

1.5m from air

 

 

 

 

note 2

note 3

kW

 

 

 

Weight

 

 

Heaviest

inlet face

H

 

A

Weight/Cell

 

 

 

 

 

kg

 

Section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010PAC2L

248

11

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010PLC2L

249

11

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010QAC2L

269

15

81

3628

 

2515

3906

2102

 

1052

 

 

 

 

 

 

MD5010QLC2L

270

15

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010RAC2L

286

18.5

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010RLC2L

289

18.5

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010PAD2L

279

11

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010PLD2L

280

11

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010QAD2L

304

15

81

3932

 

2820

4069

2265

 

1213

 

 

 

 

 

 

MD5010QLD2L

305

15

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010RAD2L

325

18.5

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010RLD2L

329

18.5

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010PAF2L

293

11

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010PLF2L

294

11

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010QAF2L

317

15

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010QLF2L

318

15

80

4237

 

3124

4256

2453

 

1376

 

 

 

 

 

 

MD5010RAF2L

341

18.5

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010RLF2L

346

18.5

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010SAF2L

360

22

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MD5010SLF2L

362

22

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

1Use this bulletin for preliminary layouts only. Obtain current drawings from your Marley sales representative. All table data is per cell.

2Last two characters of the model number indicate number of cells and cell configuration. Change as appropriate for your selection.

3Nominal tons are based upon 35°C HW, 29.5°C CW, 25.5°C WB and .68 m3/hr per ton. The Marley UPDATE web-based selection software provides MD model recommendations based on specific design requirements.

4Standard overflow is a 3" dia. M connection located on the side of the collection basin. Makeup water connection is 2" dia. M connection located on the side of the tower. A 3" M drain connection is located on the side of the collection basin.