Convenience and Safety Options

Marley / MD CoolingTower / Specifications: Options

34

 

Specifications

 

Specification Value

 

Convenience and Safety Options

 

 

 

Mechanical Access Platform:

 

 

10.2 Add the following paragraph in

 

Periodic inspection and maintenance of a cooling tower distribution sys-

 

the Access section: There shall be

 

tem is fundamental to preserving maximum cooling system efficiency.

 

a mechanical access platform at the

 

All cooling towers—crossflow or counterflow—are subject to clogging

 

mechanical access door allowing

 

to varying degrees by waterborne contaminants such as pipe scale and

 

access to the mechanical system, drift

 

sediment. Therefore, safe and easy access to these components is of

 

eliminators, distribution system and fill.

 

significant value to the operator.

 

The platform shall be galvanized steel

 

Access can be provided in a number of ways, including portable lad-

 

bar grating, supported by galvanized

 

 

steel framework attached to the tower.

 

ders or scaffolding, but for maximum safety and convenience, a field

 

The platform shall be surrounded by

 

installed Marley access platform with guardrails is available to make

 

a guardrail, kneerail, and toeboard

 

this task as safe and user-friendly as possible. Further, its location on

 

designed according to meet local

 

the side of the tower does not add to the height of the unit, preserving

 

safety requirements. A ladder shall be

 

architectural integrity. It also saves the owner time and money, in that

 

permanently attached to the platform

 

maintenance personnel may devote their time to inspection rather than

 

and to the casing of the tower, rising

 

searching for ladders or erection of portable scaffolding.

 

from the base of the tower to the top

 

 

 

of the handrail.

 

 

 

Ladder Extension:

 

 

10.2 Add the following to the end of para-

 

Many cooling towers are installed such that the base of the unit is 60cm

 

graph 10.2: Provide a ladder extension

 

or more above the roof or grade level. This makes it difficult to get up

 

for connection to the foot of the ladder.

 

to the foot of the attached ladder. The ladder extension alleviates this

 

This extension shall be long enough to

 

problem. Marley ladder extensions are available in standard 1.5m and

 

rise from the roof (grade) level to the

 

3.5 lengths.

 

base of the cooling tower. The install-

 

 

 

ing contractor shall be responsible for

 

 

 

cutting the ladder to length; attaching it

 

 

 

to the foot of the cooling tower ladder;

 

 

 

and anchoring it at its base.

 

 

 

Ladder Safety Cage:

 

 

10.3 Add the following paragraph in the

 

 

 

Access section: A welded aluminum

 

 

 

safety cage shall surround the ladder,

 

 

 

extending from a point approximately

 

 

 

2m above the foot of the ladder to the

 

 

 

top of the handrail.

 

 

 

 

 

 

Page 34
Image 34