Marley / MD CoolingTower / Specifications: Options
34
| Specifications |
| Specification Value |
| Convenience and Safety Options |
|
|
| Mechanical Access Platform: |
|
|
10.2 Add the following paragraph in |
| ■ Periodic inspection and maintenance of a cooling tower distribution sys- | |
| the Access section: There shall be |
| tem is fundamental to preserving maximum cooling system efficiency. |
| a mechanical access platform at the |
| All cooling |
| mechanical access door allowing |
| to varying degrees by waterborne contaminants such as pipe scale and |
| access to the mechanical system, drift |
| sediment. Therefore, safe and easy access to these components is of |
| eliminators, distribution system and fill. |
| significant value to the operator. |
| The platform shall be galvanized steel |
| Access can be provided in a number of ways, including portable lad- |
| bar grating, supported by galvanized |
| |
| steel framework attached to the tower. |
| ders or scaffolding, but for maximum safety and convenience, a field |
| The platform shall be surrounded by |
| installed Marley access platform with guardrails is available to make |
| a guardrail, kneerail, and toeboard |
| this task as safe and |
| designed according to meet local |
| the side of the tower does not add to the height of the unit, preserving |
| safety requirements. A ladder shall be |
| architectural integrity. It also saves the owner time and money, in that |
| permanently attached to the platform |
| maintenance personnel may devote their time to inspection rather than |
| and to the casing of the tower, rising |
| searching for ladders or erection of portable scaffolding. |
| from the base of the tower to the top |
|
|
| of the handrail. |
|
|
| Ladder Extension: |
|
|
10.2 Add the following to the end of para- |
| ■ Many cooling towers are installed such that the base of the unit is 60cm | |
| graph 10.2: Provide a ladder extension |
| or more above the roof or grade level. This makes it difficult to get up |
| for connection to the foot of the ladder. |
| to the foot of the attached ladder. The ladder extension alleviates this |
| This extension shall be long enough to |
| problem. Marley ladder extensions are available in standard 1.5m and |
| rise from the roof (grade) level to the |
| 3.5 lengths. |
| base of the cooling tower. The install- |
|
|
| ing contractor shall be responsible for |
|
|
| cutting the ladder to length; attaching it |
|
|
| to the foot of the cooling tower ladder; |
|
|
| and anchoring it at its base. |
|
|
| Ladder Safety Cage: |
|
|
10.3 Add the following paragraph in the |
|
| |
| Access section: A welded aluminum |
|
|
| safety cage shall surround the ladder, |
|
|
| extending from a point approximately |
|
|
| 2m above the foot of the ladder to the |
|
|
| top of the handrail. |
|
|
|
|
|
|