SPX Cooling Technologies Marley MD specifications Offset May Be Required

Models: Marley MD

1 40
Download 40 pages 61.95 Kb
Page 25
Image 25
OFFSET MAY BE REQUIRED

Marley / MD CoolingTower / Engineering Data : Hoisting

25

OFFSET MAY BE REQUIRED

OFFSET MAY BE REQUIRED

 

FOR BALANCED LIFT

FOR BALANCED LIFT

 

CENTER OF

CENTER OF

 

TOWER

TOWER

 

 

LIFTING

LIFTING

 

SLING

SLING

WIDTH

WIDTH

 

 

 

70° MAX

 

 

BOTH MODULES

 

 

Base Module

 

 

Top Module

 

Model

 

 

 

 

 

 

Width

Sling Length

Weight

Width

Sling Length

Weight

 

 

Minimum

kg

Minimum

kg

 

 

 

 

 

 

 

 

 

 

MD5008

2.6m

3m

1100

2.8m

3m

900

 

 

 

 

 

 

 

MD5010

2.6m

4m

1350

2.6m

3m

1050

 

 

 

 

 

 

 

MD5016

3.7m

4m

1650

3.7m

3m

1750

 

 

 

 

 

 

 

NOTE

1Hoisting operations can be dangerous and suitable safety precautions should be taken to protect personnel and the equipment being hoisted.

2All hoisting equipment should be certified and comply with local and national safety regulations.

3Ensure that slings are of sufficient length so not to impose bending loads onto the casing—use of spreader bars is essential.

4For overhead lifts or where additional safety is required, add slings beneath the tower unit