SPX Cooling Technologies Marley MD Marley / MD CoolingTower / Specifications Base, Access

Models: Marley MD

1 40
Download 40 pages 61.95 Kb
Page 32
Image 32
Specification Value

Marley / MD CoolingTower / Specifications: Base

32

 

Specifications

 

Specification Value

10.0

Access:

 

 

10.1

A large rectangular access door shall

 

 

 

be located in the plenum on the motor

 

 

 

side of the tower.

 

 

11.0

Cold Water Collection Basin:

 

 

11.1

The collection basin shall be heavy-

 

The MD tower design offers side-suction as standard. Bottom outlets

 

gauge galvanized steel and shall

 

may be supplied to accommodate a variety of piping schemes. Unless

 

include the number and type of suction

 

so specified, the tower you may be asked to approve may only be avail-

 

connections required to accommodate

 

able with one type of suction connection requiring you to redesign your

 

the out-flow piping system shown on

 

piping layout.

 

the plans. Suction connections shall be

 

The sloping floor and low-level drain is valuable because it provides a

 

equipped with debris screens. A fac-

 

 

tory installed, float operated, mechani-

 

way to achieve flush-out cleanability.

 

cal make-up valve shall be included.

 

 

 

An overflow and drain connection shall

 

 

 

be provided in each cell of the tower.

 

 

 

The basin floor shall slope toward the

 

 

 

drain to allow complete flush out of

 

 

 

debris and silt which may accumu-

 

 

 

late. Towers of more than one cell

 

 

 

shall include steel flumes for flow and

 

 

 

equalization between cells.

 

 

13.0

Warranty:

 

 

13.1

The MD cooling tower shall be free

 

 

 

from defects in materials and work-

 

 

 

manship for a period of eighteen (18)

 

 

 

months from the date of shipment.

 

 

 

 

 

 

Page 32
Image 32