Specifications

 

Specification Value

 

Control Options

 

 

 

Fan Motor Starter Control Panel:

 

 

6.4

Add the following paragraph in

 

If it is your opinion that the control system for the cooling tower

 

the Mechanical Equipment sec-

 

be part of the cooling tower manufacturer’s responsibility, we are

 

tion: Each cell of the cooling tower

 

in wholehearted agreement with you. Who better to determine the

 

shall be equipped with a UL listed

 

most efficient mode and manner of a cooling tower’s operation—

 

control system in a IP52 or IP56 out-

 

and to apply a system most compatible with it—than the designer

 

door enclosure capable of controlling

 

and manufacturer of the cooling tower?

 

single-speed or two-speed motors as

 

Marley variable speed drives are also available for the ultimate in

 

required, and designed specifically for

 

 

cooling tower applications. The panel

 

temperature control, energy management, and mechanical equip-

 

shall include a main fused discon-

 

ment longevity.

 

nect or main circuit breaker with an

 

 

 

external operating handle, lockable in

 

 

 

the off position for safety. Across-the-

 

 

 

line magnetic starters or solid-state

 

 

 

soft-start starters as required shall

 

 

 

be controlled with a thermostatic or

 

 

 

solid-state temperature controller.

 

 

 

Door mounted selector switches shall

 

 

 

be provided to enable automatic or

 

 

 

manual control and wired to meet local

 

 

 

control voltage. If required, control cir-

 

 

 

cuit to be wired out to terminal blocks

 

 

 

for field connection to a remote vibra-

 

 

 

tion switch, overload trip alarms and

 

 

 

remote temperature control devices.

 

 

 

The temperature controller shall be

 

 

 

adjustable for the required cold-water

 

 

 

temperature. If a thermostatic control-

 

 

 

ler is used it shall be mounted on the

 

 

 

side of the tower with the temperature

 

 

 

sensing bulb installed in the cold water

 

 

 

basin using a suspension mounting

 

 

 

bracket. If a solid-state temperature

 

 

 

controller is used the controller will be

 

 

 

door mounted on the control panel.

 

 

 

The temperature controller will display

 

 

 

two temperatures, one for outgoing

 

 

 

water and the other for set point.

 

 

 

Water temperature input shall be

 

 

 

obtained using a three-wire RTD with

 

 

 

dry well in the outlet water piping and

 

 

 

wired back to the solid-state tempera-

 

 

 

ture controller in the control panel.

 

 

 

 

 

 