Specifications

Specification Value

1.0Base:

28

1.1

Furnish and install an induced-draft,

Your specification base establishes the type, configuration, base materi-

 

counterflow-type, factory assembled,

al, and physical limitations of the cooling tower to be quoted. During the

 

film fill, industrial duty, cooling tower.

planning and layout stages of your project, you will have focused your

 

Unit shall consist of _____ cell(s), as

attention on a cooling tower selection that fits your space allotment, and

 

shown on plans. The limiting overall

whose power usage is acceptable. Limitations on physical size and total

 

dimensions of the tower shall be _____

operating horsepower avoid the introduction of unforeseen operational

 

wide, _____ long, and _____ high. Total

and site-related influences. Specifying the number of cells, and the max-

 

operating power of all fans shall not

imum fan hp/cell will work to your advantage.

 

exceed _____ kW, consisting of_____

You are specifying a counterflow tower, which is a type noted—and usu-

 

@ _____ kW motor(s). Tower shall be

ally specified—for its economical use of plan area on projects where

 

Marley Model _____________________.

the required thermal performance is very difficult. It effectively replaces

 

 

most makes of older towers—both forced-draft and induced-draft—with-

 

 

out major redesign of the existing site.

2.0Thermal Performance:

2.1

The tower shall be capable of cool-

CTI Certification means that the cooling

 

ing _____ m3/hr of water from ____

tower has been tested under operat-

 

°C to _____ °C at a design entering

ing conditions and found to perform as

 

air wet-bulb temperature of _____ °C.

rated by the manufacturer under those

 

The thermal performance rating shall

circumstances. It assures the buyer that

 

be Certified by the Cooling Technology

the tower is not intentionally or inadver-

 

Institute. Tower shall comply with all

tently undersized by the manufacturer.

 

ASHRAE 90.1 standards.

 

3.0Performance Warranty:

3.1

CTI Certification notwithstanding, the

However, CTI certification alone is not sufficient to assure you that the

 

cooling tower manufacturer shall guar-

cooling tower will perform satisfactorily in your situation. Certification

 

antee that the cooling tower supplied

is established under relatively controlled conditions, and cooling towers

 

will meet the specified performance

seldom operate under such ideal circumstances. They are affected by

 

conditions when the tower is installed

nearby structures, machinery, enclosures, effluent from other sources,

 

as shown on the plans. If, because of

etc. Responsible and knowledgeable bidders will take such site-specific

 

a suspected thermal performance defi-

effects into consideration in selecting the cooling tower—but the speci-

 

ciency, the owner chooses to conduct

fier must insist by the written specification that the designer/manufac-

 

an on-site thermal performance test

turer guarantee this “real world” performance. Any reluctance on the

 

under the supervision of a qualified,

part of the bidder should cause you some concern.

 

disinterested third party in accordance

 

 

with CTI, ASME or other applicable

 

 

standards during the first year of oper-

 

 

ation; and if the tower fails to perform

 

 

within the limits of test tolerance; then

 

 

the cooling tower manufacturer will

 

 

pay for the cost of the test and will

 

 

make such corrections as are appro-

 

 

priate and agreeable to the owner to

 

 

compensate for the performance defi-

 

 

ciency.

 