Marley / MD CoolingTower / Specifications: Options
Specifications | Specification Value |
38
start and stop control, bypass/VFD selec- tion, Auto/Manual selections, manual speed control. To prevent heating prob- lems in the cooling tower fan motor and to assure proper gear reducer lubrication the VFD system shall de energize the motor once 25% motor speed is reached and cooling is no longer required. The cooling tower manufacturer shall supply VFD
Miscellaneous Options
Equalizer Flume Weir Gates:
11.2Add the following paragraph under Cold Water Collection Basin: The interconnecting flume between cells shall be equipped with a removable cover plate to permit the shutdown of one cell for maintenance purposes, or to permit independent cell operation.
Premium Efficiency Motor
6.3Replace paragraph 6.3 with the fol- lowing: The complete mechanical equipment assembly for each cell shall be supported by a rigid,
■Where it is your intention to be able to operate both cells of the tower while the flume cover plate is installed, separate outlet connections, float valves and overflows must be provided for each cell. Likewise, this would require separate sensors and controls for basin heater systems, if installed.
■IEC premium efficiency motor with a five year warranty enhances the standard five year mechanical equipment warranty of the MD cooling tower.