Marley / MD CoolingTower / Specifications: Base
Specifications | Specification Value |
30
shall be driven through a
6.2Motor(s) shall be ____ kW maximum,
TEFC, variable torque, inverter duty and specially insulated for cooling tower duty. Speed and electrical char- acteristics shall be ______ RPM, single- winding, ___ phase, ____ hertz, ____
volts. Motor nameplate power shall not be exceeded at design operation. TEAO motors are not acceptable.
6.3The complete mechanical equipment assembly for each cell shall be support- ed by a rigid,
(pulleys). For
18 months.
sheaves, power band belts and
TEFC motors offer additional benefits over TEAO motors whose only source of cooling is the flow of air produced by the cooling tower fan. This air rate is not always ideal due to motor position, blockage, etc. TEFC ensures the motor will always be cooled properly.
Unless otherwise specified, motor speed will be 1500 RPM in on stan- dard models. Low noise models will use motor speeds appropriate for the specific model. If you prefer the operating flexibility of
The value of a 5 year mechanical equipment warranty speaks for itself. Except for the motor, virtually all of the mechanical equipment on a Marley tower is designed and manufactured by SPX Cooling Technologies. Cooling tower vendors who purchase commercial fans, gear reducers, driveshafts, etc. may require that you deal directly with those commercial suppliers for warranty satisfaction.