8.4. Connection of Return Air Cooler (Optional)

STT40 / STT70

8.4. Connection of Return Air Cooler (Optional)

)A return air cooler must be used if the return air temperature is higher than 149°F (+65 °C).

You can connect the return air cooler to a coolant circuit or to the water main network. The water flow rate in the water main network* is for:

STT40

approx. 7.16 ft3 (0.2 m3/h),

STT70

approx. 14.13 ft3 (0.4 m3/h)

(*water temperature:42.8°F) (+6 °C) Rate your coolant circuit accordingly.

Connect the coolant in- and outlets to the return air cooler. Observe the flowing direction of the coolant.

Check the tightness of the connections. Connections are made with ½” NPT.

Figure 15: Connection of Return Air Cooler STT40 (A) / STT70 (B)

Assembly instructions 8-4