10-Pump, 80-Station Controller Chapter 4: Operation 59
shutdown delay, alarms, or blowback to the standby pump. Mechanical connections must be
changed manually.
To transfer stations from a pump to a standby pump:
1. At any screen, touch Pumps.
The Pump Status screen appears.
2. Both the source pump and the standby pump must be offline. If either pump is any
other state, disable it by touching its icon briefly.
The icon becomes grey.
3. Move the vacuum hose from the failed pump to the standby pump, and carry out any
other mechanical procedures needed to use the standby pump.
4. At the Pump Status screen, touch and hold the icon for any pump until the Pump n
Setup screen appears.
5. At the Pump n Setup screen, touch Transfer Stations To Standby Pump.
The Transfer to Standby Pump screen appears:
6. Touch Source Pump.
A list of available pumps pops up.
7. Scroll through the list to choose a source pump. Press Return once you have selected
and highlighted your desired source pump.
The number appears under Source Pump.
8. Touch Destination Pump.
A list of available pumps pops up.
9. Scroll through the list of pumps to choose a destination pump. Press Return once you
have selected and highlighted your desired destination pump.
The number appears under Standby Pump, and a button labeled Press to
Move Stations appears on the screen: