10-Pump, 80-Station Controller Chapter 8: Appendix 88
about 10 seconds. If a firmware upgrade is required, this will take about 2-3 minutes. Do not
turn off power until the upgrade completes.
Fig 8
11. Turn off power to the control enclosure. Wait 5 seconds. Turn on power.
12. Go to the System Setup Screen by pressing the System Setup button on any screen.
13. Go to the Save / Restore Screen by pressing the Save / Restore button on the right side of the
screen.
14. Restore Settings by pressing the yellow Restore Settings button.
15. Wait for the “Restore Complete” message. (This message is only displayed for 10 seconds).
16. Remove compact flash card labeled PLC Configure 744.00130.00 from the PLC CPU by
pressing the retaining clip to the right and pulling the compact flash card straight out.
17. Insert the operation compact flash card containing the new version of the software labeled PLC
Operate 744.00131.00 into the PLC CPU.
18. Save Settings by pressing the yellow Save Settings button.
19. Wait for the “Save Complete” message. (This message is only displayed for 10 seconds).
20. Go to the System Setup Screen (Fig 6) by pressing the System Setup button.
21. Verify that the clock has the correct time. If not, set the correct time by pressing the Set Time &
Date button.