10-Pump, 80-Station Controller Chapter 6: Configurable Settings 65
Name Description Options Default
Partial convey When this option is enabled, the controller
issues a “partial convey” alarm if it has
repeatedly attempted to convey material to the
station, and material has moved from the station
into the receiver, but the volume-fill proximity
sensor has never signaled that the station is full.
(The number of attempts is controlled by the
next setting.)
For a volume-fill station, this option should
usually be enabled. At times, you may wish to
disable it during operation as a stopgap
measure for dealing with an alarm. For a time-fill
station, disable this option.
disabled,
enabled disabled
# attempts B4 alarm Number of attempts before alarm: the number of
times the controller will attempt to convey
material to a station before it issues a “partial
convey” alarm.
The setting for this option depends on the same
considerations as those given above for number
of attempts before a “no convey” alarm.
1–99 3
Option Input
Receiver low level When this option is enabled, the controller
issues a “receiver level” alarm if material in the
receiver drains below the level of the receiver’s
low-level sensor.
Enable this option if and only if your facility has
installed a low-level sensor for this station’s
receiver. At times, you may wish to disable it
during operation as a stopgap measure for
dealing with an alarm.
disabled,
enabled disabled
Bypass switch When this option is enabled, a switch at the
station is used to disable/”bypass” the station.
Grinder empty When this option is enabled, a proximity switch
is used to verify that material is present in the
grinder bin. The station will only be conveyed to
when the receiver is empty and the grinder bin
has material.
Grinder empty with
Alarm When this option is enabled, alarm monitoring is
added to the grinder empty option described
above. If the grinder bin has material and the
receiver is full, a “grinder full” alarm is
generated.
Option output
Local alarm When this option is enabled, the controller turns
on the local alarm light for any alarm at this
specific station.
Enable this option if and only if your facility has
installed a local alarm light for this station.
disabled,
enabled disabled
Blow back When this option is enabled, the controller
periodically sends compressed air backward
through the station’s air filter to dislodge
accumulated dust and debris.
Enable this option if and only if the station has
the equipment for compressed air filter cleaning.
disabled,
enabled disabled