Stovax PR0731 manual Servicing Instructions, Servicing / Fault Finding Charts, Ignition Functional

Models: PR0731

1 26
Download 26 pages 20.52 Kb
Page 16
Image 16
SERVICING INSTRUCTIONS
REPLACE BATTERIES BEFORE ATTEMPTING TO RECTIFY ANY FAULTS.
IF THE FIRE DOES NOT WORK, BUT HAS WORKED IN THE PAST:
• CHECK THE EMERGENCY SHUT OFF SWITCH ON THE BOTTOM OF THE APPLIANCE IS SWITCHED ON, SEE USER SECTION, PAGE 6
Electronic Control Valve Fault Analysis

SERVICING INSTRUCTIONS

SERVICING / FAULT FINDING CHARTS

1. SERVICING REQUIREMENTS

This appliance must be serviced at least once a year by a competent person.

All tests must be serviced by best practice as described by the current CORGI recommendations.

1.1Before any tests are undertaken on the appliance:

Conduct a gas soundness test for the property to ensure there are no gas leaks prior to starting work.

1.2• Fully check the operation of the appliance

Special checks

1.2.1Clean any lint or fluff from the pilot

1.2.2Clean away any fluff or lint from under the burner

1.2.3Check the spark gap on the pilot is correct

Correct any faults found during the initial tests

Re-commission the appliance conducting the usual safety checks

1.3Advise the customer of any remedial action taken.

Symptom

Cause
Remedy

3 Short beeps from

Batteries low in

Replace appliance

control

appliance

batteries

 

 

 

No ignition, 5 second

1. On/Off switch is in

1. Move switch to

continuous tone (there

OFF position

ON position

may be several short

2. Loose/damaged

2 Check interuptor

beeps before)

wire

bloack and wires

 

 

 

No ignition, no tone,

Receiver board

Replace receiver

motor turns slightly when

damaged

 

operated

 

 

 

 

 

No pilot flame and

Thermocouple circuit

Correct wiring

control continues to

wired incorrectly

 

spark

 

 

 

 

 

Pilot lights, control

1. No spark at pilot

1. Rectify spark at

continues to spark, value

burner

pilot burner

shuts down after 10 - 30

2. Loose/damaged

2. Check interrupter

seconds

wire

and wires

CHECK 1

pilot assembly, clean the area.

Yes

Does the pilot light?

No

Is the control being operated correctly?

Yes

Will the pilot light with a match?

No

 

 

 

gas turned on to the appliance?

Yes

gas pressure correct?

 

 

Is the

 

 

Is the

Yes

Has the system got any air in it?

 

 

No

inlet test point, the leads for correct connection

SYSTEM OK

IGNITION FUNCTIONAL

PILOT WILL NOT LIGHT

around the

short the spark,

there is no debris

etc.) which could

Ensure

(e.g. soot,

Yes

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operate the valve. Is there a spark?

 

Consult User Instructions and retry.

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

Yes

Check alignment of pilot burner head, change the ignition lead. Change the electrode See Replacing Parts, section 5.

No

 

 

No

 

 

 

 

 

 

 

 

 

 

 

Check isolation tap and gas meter, retry.

 

 

 

 

 

 

 

Correct and retry.

 

 

 

 

 

Yes

Purge the gas pipes and retry.

is a blockage in the system, check the seating and valve. Check thermocouple

orientation, condition and

There mag

 

GO TO THE NEXT CHART, IGNITION FUNCTIONAL CHECK 2

16

Page 16
Image 16