48 Netra ft 1800 Installation Guide • February 1999
Required Connection MaterialsDC branch circuits:
■The required number of field wiring kits aresupplied in the shipkit with each
system, according to configuration.
Grounding:
■One Thomas & Betts two-hole lug (part number: 54204-UB) suitable for 8 AWG
conductor or UL/CSA approved equivalent having 5/8-inch pitch; torque value:
3.5 Nm maximum.
■A Thomas & Betts crimping tool (part number: TBM 5-S), or approvedequivalent
to secure the lug on to the cable.
■A grounding bus bar that is near the equipment and easily accessible.
Dual Grounding Environment:
■Additional Thomas & Betts two-hole lug for logic 0V studs.
Caution – External filtering and/or surge suppression devices may be requiredon
the power feeds where branch circuit electromagnetic characteristics areunknown.
DC Supply and Ground ConductorThe requirements are:
■Suitable conductor material: copper only.
■Supply conductors: 8 AWG(6 mm2) (between the Netra ft 1800 and the circuit
breaker).
■Ground conductor: 8 AWG.
■Cable insulation rating: minimum 75 degrees Celsius, Low Smoke Fume (LSF),
Flame Retardant.
■Cable type must be one of:
■UL style 1028 or other UL 1581 compliant equivalent.
■IEEE 383 compliant.
■IEEE 1202-1991 compliant or classified.
■Branch circuit cable insulation color: per applicable national electrical codes.
■Grounding cable insulation color: green/yellow.
!