DC Source Site Requirements
The DC source site requirements are as follows:
■Suitable for use in
■The supply source must be electrically isolated by double or reinforced insulation from any hazardous AC or DC source.
■The DC source must be reliably connected to earth (that is, battery room positive bus is connected to the grounding electrode).
■The DC source must be capable of providing up to 925W of continuous power per feed pair. The sum of all three feeds on one side will be less than 1500W for
Overcurrent Protection Requirements
Overcurrent protection devices must be provided as part of each host equipment rack.
Circuit breakers meeting the requirements shown in TABLE
TABLE 3-1 Overcurrent Protection Requirements
Current rating | 30A maximum |
Voltage | Maximum 60 Vdc rated in |
| Maximum 75 Vdc rated in |
Type | Fast trip |
Protection | Double pole breaking (both grounded and ungrounded conductor |
| open on fault) |
Contact gap | Minimum 3 mm |
Nuisance tripping | Circuit breaker must not operate when presented with an inrush |
| current of 27 amps and a duration of 2.5 microseconds |
Quantity | One per feed, up to 12 per system |
|
|