Sunlife Enterprises DM240, DM300, DM180 installation manual Clearances

Models: DM300 DM240 DM180

1 56
Download 56 pages 41.42 Kb
Page 25
Image 25
Manual background

356214-XIM-A-0108

CLEARANCES

 

NOTE:

ELEC / ELEC Models: Units and ductwork are

 

 

 

approved for zero clearance to combustible material

LOCATION

CLEARANCE

 

when equipped with electric heaters.

Front

914 / 36”

 

Rear

610 / 24” (Less Economizer)

 

GAS / ELEC Models: A 25mm/1” clearance must be

1245 / 49” (With Economizer)

 

provided between any combustible material and the

 

 

 

Left Side (Filter Access)

610 / 24” (Less Economizer)

supply air ductwork for a distance of .9 meter/3 feet

1372 / 54” (With Economizer)3

 

 

 

from the unit.

Right Side (Cond. Coil)

914 / 36”

 

 

Below Unit1

0 / 0”

 

The products of combustion must not be allowed to

 

1829 / 72” With 914 / 36”

Above Unit2

accumulate within a confined space and recirculate.

Maximum Horizontal Overhang

 

 

(For Condenser Air Discharge)

Locate unit so that the vent air outlet hood is at

 

 

 

1. Units may be installed on combustible floors made from wood

least:

or class A, B, or C roof covering material.

 

2.Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.

3.If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of evapo- rator coil, or in the outdoor air compartment, prior to final instal- lation.

9 meters/3 feet above any force air inlet located within 3.0 meters/10 horizontal feet (excluding those integral to the unit).

1.2 meters/4 feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.

 

 

ECONOMIZER

 

 

MOTORIZED

SUPPLY AIR

POWER EXHAUST

DAMPER

RAIN HOOD

RAIN HOOD

COMPARTMENT

(on Return Air Compartment)

(on Outdoor Air Compartment)

 

930

(36-5/8”)

127 (5”)

1.2 meters/4 feet from electric and gas meters, regulators and relief equipment.

ECONOMIZER / MOTORIZED DAMPER

AND POWER EXHAUST RAIN HOODS

FIXED OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment)

410

25 (1“) CONDENSATE

DRAIN

(16-1/8”)

(Must be trapped)

 

716

2337

(28-3/16”)

(92”)

REAR VIEW

LH VIEW

DETAIL “Y”

UNIT WITH RAIN HOODS

FIGURE 15 - UNIT CLEARANCES AND RAIN HOOD DIMENSIONS (15, 20 & 25 TON)

Johnson Controls Unitary Products

25