TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - COOLING APPLICATIONS 300 MBH - BOTTOM DUCT CONNECTIONS
DM300 UNIT - DOWNFLOW DUCT CONNECTIONS (CFM)
BLOWER | PULLEY |
| 7500 CFM |
|
| 8750 CFM |
|
| 10000 CFM |
| |
|
|
|
|
|
|
|
|
|
| ||
SPEED (rpm) | TURNS OPEN | ESP (iwg) | OUTPUT (bhp) |
| INPUT (kW) | ESP (iwg) | OUTPUT (bhp) | INPUT | ESP (iwg) | OUTPUT (bhp) | INPUT |
|
|
|
|
|
|
|
| (kW) |
|
| (kW) |
945 | 6.0 | 1.2 | 5.6 |
| 4.6 | 0.8 | 7.0 | 5.7 | 0.3 | 8.4 | 6.9 |
|
|
|
|
|
|
|
|
|
|
|
|
975 | 5.0 | 1.4 | 5.9 |
| 4.9 | 1.0 | 7.3 | 6.0 | 0.5 | 8.8 | 7.2 |
|
|
|
|
|
|
|
|
|
|
|
|
1005 | 4.0 | 1.6 | 6.2 |
| 5.1 | 1.2 | 7.7 | 6.3 | 0.7 | 9.2 | 7.6 |
|
|
|
|
|
|
|
|
|
|
|
|
1040 | 3.0 | 1.8 | 6.6 |
| 5.4 | 1.4 | 8.1 | 6.7 | 0.9 | 9.7 | 8.0 |
|
|
|
|
|
|
|
|
|
|
|
|
1070 | 2.0 | 2.0 | 6.9 |
| 5.7 | 1.6 | 8.5 | 7.0 | 1.1 | 10.2 | 8.3 |
|
|
|
|
|
|
|
|
|
|
|
|
1100 | 1.0 | 2.1 | 7.3 |
| 6.0 | 1.8 | 8.9 | 7.3 | 1.3 | 10.6 | 8.7 |
|
|
|
|
|
|
|
|
|
|
|
|
1130 | 0.0 | 2.3 | 7.6 |
| 6.2 | 2.0 | 9.3 | 7.6 | 1.5 | 11.0 | 9.0 |
|
|
|
|
|
|
|
|
|
|
|
|
DM300 UNIT - DOWNFLOW DUCT CONNECTIONS (m3/s) |
|
|
|
|
|
|
| ||||
BLOWER | PULLEY |
| 3.53 m3/Sec. |
|
| 4.13 m3/Sec. |
|
| 4.72 m3/Sec. |
| |
SPEED (rpm) | TURNS OPEN | ESP (Pa) | OUTPUT (bhp) |
| INPUT (kW) | ESP (Pa) | OUTPUT (bhp) | INPUT | ESP (Pa) | OUTPUT(bhp) | INPUT |
|
|
|
|
|
|
|
| (kW) |
|
| (kW) |
945 | 6.0 | 303 | 5.6 |
| 4.6 | 198 | 7.0 | 5.7 | 71 | 8.4 | 6.9 |
|
|
|
|
|
|
|
|
|
|
|
|
975 | 5.0 | 347 | 5.9 |
| 4.9 | 244 | 7.3 | 6.0 | 120 | 8.8 | 7.2 |
|
|
|
|
|
|
|
|
|
|
|
|
1005 | 4.0 | 391 | 6.2 |
| 5.1 | 291 | 7.7 | 6.3 | 169 | 9.2 | 7.6 |
|
|
|
|
|
|
|
|
|
|
|
|
1040 | 3.0 | 443 | 6.6 |
| 5.4 | 347 | 8.1 | 6.7 | 228 | 9.7 | 8.0 |
|
|
|
|
|
|
|
|
|
|
|
|
1070 | 2.0 | 489 | 6.9 |
| 5.7 | 396 | 8.5 | 7.0 | 280 | 10.2 | 8.3 |
|
|
|
|
|
|
|
|
|
|
|
|
1100 | 1.0 | 536 | 7.3 |
| 6.0 | 445 | 8.9 | 7.3 | 332 | 10.6 | 8.7 |
|
|
|
|
|
|
|
|
|
|
|
|
1130 | 0.0 | 583 | 7.6 |
| 6.2 | 495 | 9.3 | 7.6 | 385 | 11.0 | 9.0 |
|
|
|
|
|
|
|
|
|
|
| |
DM300 UNIT - | DOWNFLOW DUCT CONNECTIONS - GAS HEAT MODELS (CFM) |
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
BLOWER | PULLEY |
| 7500 CFM |
|
| 8750 CFM |
|
| 10000 CFM |
| |
|
|
|
|
|
|
|
|
|
| ||
SPEED (rpm) | TURNS OPEN | ESP (iwg) | OUTPUT (bhp) |
| INPUT (kW) | ESP (iwg) | OUTPUT (bhp) | INPUT | ESP (iwg) | OUTPUT (bhp) | INPUT |
|
|
|
|
|
|
|
| (kW) |
|
| (kW) |
945 | 6.0 | 1.0 | 5.6 |
| 4.6 | 0.3 | 7.0 | 5.7 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
975 | 5.0 | 1.2 | 5.9 |
| 4.9 | 0.5 | 7.3 | 6.0 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
1005 | 4.0 | 1.4 | 6.2 |
| 5.1 | 0.7 | 7.7 | 6.3 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
1040 | 3.0 | 1.6 | 6.6 |
| 5.4 | 0.9 | 8.1 | 6.7 | 0.2 | 9.7 | 8.0 |
|
|
|
|
|
|
|
|
|
|
|
|
1070 | 2.0 | 1.8 | 6.9 |
| 5.7 | 1.1 | 8.5 | 7.0 | 0.4 | 10.2 | 8.3 |
|
|
|
|
|
|
|
|
|
|
|
|
1100 | 1.0 | 2.0 | 7.3 |
| 6.0 | 1.3 | 8.9 | 7.3 | 0.6 | 10.6 | 8.7 |
|
|
|
|
|
|
|
|
|
|
|
|
1130 | 0.0 | 2.2 | 7.6 |
| 6.2 | 1.5 | 9.3 | 7.6 | 0.8 | 11.0 | 9.0 |
|
|
|
|
|
|
|
|
|
|
| |
DM300 UNIT - DOWNFLOW DUCT CONNECTIONS - GAS HEAT MODELS (m3/s) |
|
|
|
|
| ||||||
BLOWER | PULLEY |
| 3.53 m3/sec. |
|
| 4.13 m3/sec. |
|
| 4.72 m3/sec. |
| |
SPEED (rpm) | TURNS OPEN | ESP (Pa) | OUTPUT (bhp) |
| INPUT (kW) | ESP (Pa) | OUTPUT (bhp) | INPUT | ESP (Pa) | OUTPUT (bhp) | INPUT |
|
|
|
|
|
|
|
| (kW) |
|
| (kW) |
945 | 6.0 | 258 | 5.6 |
| 4.6 | 87 | 7.0 | 5.7 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
975 | 5.0 | 301 | 5.9 |
| 4.9 | 133 | 7.3 | 6.0 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
1005 | 4.0 | 345 | 6.2 |
| 5.1 | 180 | 7.7 | 6.3 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
1040 | 3.0 | 398 | 6.6 |
| 5.4 | 236 | 8.1 | 6.7 | 43 | 9.7 | 8.0 |
|
|
|
|
|
|
|
|
|
|
|
|
1070 | 2.0 | 444 | 6.9 |
| 5.7 | 285 | 8.5 | 7.0 | 94 | 10.2 | 8.3 |
|
|
|
|
|
|
|
|
|
|
|
|
1100 | 1.0 | 490 | 7.3 |
| 6.0 | 334 | 8.9 | 7.3 | 146 | 10.6 | 8.7 |
|
|
|
|
|
|
|
|
|
|
|
|
1130 | 0.0 | 537 | 7.6 |
| 6.2 | 384 | 9.3 | 7.6 | 199 | 11.0 | 9.0 |
|
|
|
|
|
|
|
|
|
|
|
|
NOTES: 1.Blower performance includes a
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.
*Do NOT close the pulley below 1 turn open.
**Factory setting.
32 | Johnson Controls Unitary Products |