Should a freezestat open three times within two hours of operation, the UCB will
LOW AMBIENT COOLING
To determine when to operate in low ambient mode, the UCB has a pair of terminals connected to a temper-
Low ambient mode operates the compressors in this manner: 10 minutes on, 5 minutes off. The indoor blower is operated throughout the cycle. The
Low ambient mode always begins with compressor operation. Compressor minimum run time may extend the minutes of compressor operation. The defrost cycle will begin immediately following the elapse of the mini- mum run time.
When operating in low ambient mode, the UCB will not lockout the compressors due to a freezestat trip. How- ever, a freezestat trip will
SAFETY CONTROLS
The unit control board monitors the following inputs for each cooling system:
1.A suction line freezestat to protect against low evaporator temperatures due to a low airflow or a low return air temperature, (opens at 26 ± 5 °F and resets at 38 ± 5°F).
2.A
3.A
The above pressure switches are
The other refrigerant system will continue in operation unless it is affected by the fault as well.
The unit control board monitors the temperature limit switch of electric heat units and the temperature limit switch and the gas valve of gas furnace units.
COMPRESSOR PROTECTION
The compressors also have inherent (internal) protec- tion. If there is an abnormal temperature rise in a com- pressor, the protector will open to shut down the compressor. The UCB incorporates features to mini- mize compressor wear and damage. An
The ASCD is initiated on unit
FLASH CODES
The UCB will initiate a flash code associated with errors within the system. Refer to UNIT CONTROL BOARD FLASH CODES Table 24.
RESET
Remove the call for cooling, by raising thermostat set- ting higher than the conditioned space temperature. This resets any pressure or freezestat flash codes.
ELECTRIC HEATING SEQUENCE OF OPERATIONS
The following sequence describes the operation of the electric heat section.
a.Upon a call for heat by the thermostat, the heater contactor (6M) will be energized. After completing the specified fan on delay for heating, the UCB will energize the blower motor.
b.The thermostat will cycle the electric heat to satisfy the heating requirements of the conditioned space.
a.Upon a call for