![MANIFOLD GAS PRESSURE ADJUSTMENT](/images/new-backgrounds/54064/5406487x1.webp)
MANIFOLD GAS PRESSURE ADJUSTMENT
Small adjustments to the
Adjust as follows:
1.Remove the cap on the regulator. It's located next to the
2.To decrease the gas pressure, turn the adjusting screw counterclockwise.
3.To increase the gas pressure, turn the adjusting screw clockwise.
NOTE: The correct manifold pressure for these fur- naces is 3.65 IWG ±0.3.
BURNERASSEMBLYBRACKET
FLAMESENSORBULB
FIGURE 22 - PROPER FLAME ADJUSTMENT
PILOT CHECKOUT
The pilot flame should envelope the end of the flame sensor. To adjust pilot flame, (1) remove pilot adjust- ment cover screw, (2) increase or decrease the clear- ance for air to the desired level, (3) be sure to replace cover screw after adjustment to prevent possible gas leakage.
Put the system into operation and observe through complete cycle to be sure all controls function properly.
BURNER INSTRUCTIONS
To check or change burners, pilot or orifices, CLOSE MAIN MANUAL
1.Remove the screws holding either end of the mani- fold to the burner supports.
2.Open the union fitting in the gas supply line just upstream of the unit gas valve and downstream from the main manual
3.Remove the gas piping closure panel.
4.Disconnect wiring to the gas valves and spark ignit- ors. Remove the
FIGURE 23 - TYPICAL FLAME APPEARANCE
Burners are now accessible for service.
Reverse the above procedure to replace the assem- blies. Make sure that burners are level and seat at the rear of the heat exchanger.
BURNER AIR SHUTTER ADJUSTMENT
Adjust burner shutters so no yellow flame is observed in the heat exchanger tubes.
CHECKING GAS INPUT
NATURAL GAS
1.Turn off all other gas appliances connected to the gas meter.
2.With the furnace turned on, measure the time needed for one revolution of the hand on the small- est dial on the meter. A typical gas meter usually has a 1/2 or a 1 cubic foot test dial.
3.Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from the Gas Rate - Cubic Feet Per Hour Table 23.
If the actual input is not within 5% of the furnace rating (with allowance being made for the permissible range
44 | Johnson Controls Unitary Products |