Thermo Products CDX3-125N, CDX3-75N, CHX3-75N, CHX3-125N C. Measuring And Adjusting Heat Input Rate

Models: CDX3-100N CHX3-100N CDX3-125N CHX3-125N CHX3-75N CDX3-75N

1 65
Download 65 pages 33.09 Kb
Page 45
Image 45
C. Measuring And Adjusting Heat Input Rate

All installations and services must be performed by qualified service personnel.

C. Measuring And Adjusting Heat Input Rate

DO NOT exceed input rating stamped on furnace nameplate or manufacturer's recommended burner manifold pressure for orifice size used.

Observe the following precautions when measuring:

A.Burner manifold pressure with a pressure gauge.

1.Close the gas valve (turn the gas control knob to the OFF position) BEFORE removing the:

a.burner manifold pressure tap plug to connect the manometer (or calibrated pressure gauge)

b.manometer, or gauge, and replacing the pressure tap plug.

2.Shut off the gas supply at the appliance service (manual gas shutoff) valve (or for LP gases, shut off the gas at the storage tank service valve) BEFORE removing the:

a.gas valve inlet pressure tap plug

b.manometer, or gauge and replacing the inlet pressure tap plug.

3.Perform a gas leakage test at the gas valve inlet and burner manifold pressure tap plugs.

B.Gas flowrate by clocking gas meter.

1.To determine the amount of flow, through the gas meter, due to the operation of the furnace.

a.Turn off all other appliances and extinguish their pilot flames, if equipped, or

b.Deduct the gas consumption of all other operating appliances from the total meter reading.

2.Convert the gas flowrate to the heat input rate (in BTUH) as described in step 10 (in the following section) and compare the value to the heat input rating on the furnace nameplate.