Thermo Products CHX3-100N, CDX3-75N, CHX3-75N, CHX3-125N, CDX3-125N, CDX3-100N operation manual

Models: CDX3-100N CHX3-100N CDX3-125N CHX3-125N CHX3-75N CDX3-75N

1 65
Download 65 pages 33.09 Kb
Page 46
Image 46
NOTICE: A U-tube manometer, measuring pressure in inches of water column, is recommended for all gas pressure measurements. However, an aneroid pressure gauge, in good working condition, capable of reading pressure changes of 0.05 in. W.G., or less, that was recently calibrated (within the last year), is a satisfactory alternate. These two (2) devices will be considered as equivalent and interchangeable. Either device is referred to below as a “pressure gauge”

All installations and services must be performed by qualified service personnel.

NOTICE: A U-tube manometer, measuring pressure in inches of water column, is recommended for all gas pressure measurements. However, an aneroid pressure gauge, in good working condition, capable of reading pressure changes of 0.05 in. W.G., or less, that was recently calibrated (within the last year), is a satisfactory alternate. These two (2) devices will be considered as equivalent and interchangeable. Either device is referred to below as a “pressure gauge”

NOTICE: This 2-stage gas valve has two separate gas pressure regulators. Checks and adjustments must be made at both high fire (high adjustment) and low fire (low adjustment).

1.Shut off the gas at the automatic gas control valve (turn gas control switch to the OFF position).

2.Remove the outlet pressure tap plug from gas burner manifold and connect a pressure gauge. Refer to Figure 22, below.

Figure 22: Exploded View of CDX/CHX Gas Control System

3.Turn on the gas at the automatic gas control valve (turn gas control switch to the ON position).

4.Adjust the room thermostat so the furnace will operate on low fire only.

40

Page 46
Image 46
Thermo Products CHX3-100N, CDX3-75N, CHX3-75N, CHX3-125N, CDX3-125N, CDX3-100N operation manual