Thermo Products OL6RA072D48(B/R), OL6FA072DV5(B/R), OL6FA072D48(B/R), OL6RA072DV5(B/R) Heat Mode

Models: OL6FX072DV5(R) OL6RX072DV5(R) OL6RA072DV5(B/R) OL6FA072D48(B/R) OL6RA072D48(B/R) OL6FA072DV5(B/R)

1 75
Download 75 pages 52.42 Kb
Page 37
Image 37
Heat Mode

Heat Mode

When a call for heat (“W”) is received from the thermostat, if the “Cool” mode is not already active, the “T-T” terminal is energized and the blower on delay is started. The on-off pattern of DIP switch SW2 (positions 1 and 2) select one of four blower on delay values (see Table 11). When the delay time has elapsed, the “HEAT” blower speed is energized. The control remains in steady heat mode until the thermostat is satisfied. When the call for heat signal is removed, the “T-T” terminal is de-energized and the blower off delay is started. The on-off pattern of DIP switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 11). When the delay time has elapsed, the “HEAT” blower speed terminal is de-energized.

DIP SWITCH 2 SECTION STATE

BLOWER DELAY TIMES

 

1

2

3

4

Counter Flow

ON - SEC

 

OFF - MIN

ON - SEC

 

 

 

 

 

 

 

 

OFF

OFF

 

 

15

30

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

24

60

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

36

120

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

48

240

 

 

 

 

 

 

 

 

 

 

 

 

OFF

OFF

 

 

 

2

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

 

4

 

 

 

 

 

 

 

 

 

 

OFF

ON

 

 

 

6

 

 

 

 

 

 

 

 

 

 

ON

ON

 

 

 

8

 

 

 

 

 

 

 

 

Table 11: ON and OFF Blower Delay Time Switch Settings

Motor Blower Speed

Three interconnected blower speed outputs are provided. A “G” call for fan will provide power to the LOW speed tap only. A “W” heat call will provide power to the Heat speed tap only. A “Y” cooling call will provide power to the Cool speed tap only.

In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the input that was first initiated. In the case where the control is in a cooling mode with both “Y” and “W” inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to the control switching into a heating mode. In the case where the control is in a heating mode with both “Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be executed prior to the control switching into a cooling mode. In the case where a call for fan “G” already exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective “W” or a “Y” speed following the blower on delay for that call.

The speed taps are interconnected and interlocked, only one speed may be powered at any one time. When a speed is to be operated, the speed select relays are operated to select the path to the motor tap and then the enable relay is operated to switch the operating power to the selected motor speed tap. If the speed of the running motor is to be changed, first the enable relay removes power from the motor, the new speed is selected and then power is restored to the motor.

Blower On and Off Delays

Four Heat blower on and four blower off delays are selected by two dip switches for each function. Refer to Table 11 for specific delay values.