H. BURNER SPECIFICATIONS AND APPLICATIONS:

H. BURNER SPECIFICATIONS AND APPLICATIONS:

 

THERMO

*

BECKETT

HEAD

STATIC

MAXIMUM

SHIPPED

OIL

 

PRIDE’S

INS

BURNER

 

PLATE

NOZZLE

NOZZLE

PUMP

FURNACE MODEL

BURNER

 

MODEL &

 

 

SIZE**

SIZE

PRESSURE

 

SPEC NO.

 

TUBE

 

 

 

 

(PSIG)

 

 

 

LENGTH

 

 

 

 

 

OL6*A072D**B

TP2501

N

AFG-4.5”

F3

3-5/8

0.75X80° H

0.60X80° H

120

 

 

 

 

 

 

 

 

 

The optional BF3 Riello flame retention oil burner can be used with OL6.

 

THERMO

 

RIELLO

HEAD

STATIC

 

PRIDE’S

INS

BURNER

 

PLATE

FURNACE MODEL

BURNER

+

MODEL &

 

 

 

SPEC NO.

 

TUBE

 

 

 

 

 

LENGTH

 

 

OL6*A072D**R

C8511325

S

BF3-4.5”

N/A

N/A

 

 

 

 

 

 

MAXIMUM NOZZLE SIZE**

0.70X80° H

SHIPPED OIL NOZZLE SIZE PUMP

PRESSURE (PSIG)

0.60X80° H

140

Table 6: Beckett & Riello burners specifications

+ INSULATOR S = SLEEVE OR N = NONE

THE NOZZLE SIZE GIVES THE NOMINAL FLOWRATE, IN GPH, FOLLOWED BY THE SPRAY ANGLE, IN DEGREE’S, AND THE SPRAY PATTERN, EITHER “H” FOR HOLLOW CONE OR “S” FOR SOLID CONE. FOR EXAMPLE, A NOZZLE RATED AT 0.65 GPH @ 100 PSIG THAT PROVIDES AN 80° SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS “0.65 X 80°H”.

For more specific burner information, contact:

Thermo Products, LLC. P.O. Box 217, North Judson, IN 46366.

Phone 574-896-2133.

OIL NOZZLE CAPACITY CHART

 

NOZZLE SIZE

EQUIVALENT HEAT

EFFECTIVE HEATING

UNITS

(GPH)

 

INPUT RATE NOTE #1

CAPACITY NOTE #2

Beckett

Riello

(BTU/HR)

(BTU/HR)

 

 

 

 

 

 

 

 

 

OL6*A060D***

.50

.50

70,000

60,000

OL6*A072D***

.60

.60

85,000

73,000

OL6*A090D***

.75

.70

106,250

90,000

Table 7: Oil nozzle capacity

All rates shown achieved with 120 PSIG pump pressure for Beckett and 140 PSIG pump pressure for Riello.