If it is necessary to troubleshoot the flame sensor independently of the burner primary, the following procedure may be used.
B. CAD CELL CHECKOUT PROCEDURE:
1.Stop burner and shutoff electrical power to the appliance.
2.Open burner junction box (on top of the burner blower) and remove the
3.Check the resistance across the cad cell pins with the cell covered (protected from exposure to ambient light). The resistance should be greater than 20,000 ohms.
4.If cell resistances are different from above, replace the
5.Carefully reinsert the
The troubleshooting chart beginning on the following page should help identify the type of malfunction or deviation from normal operation. To use this diagram, just follow the instructions in the boxes. If the answer is yes or the condition is true, go down to the next box. If the answer is no or the condition is false, go to the box on the right. Continue checking and answering questions and conditions in each box until a problem and/or repair is found. After any maintenance or repair, the trouble shooting sequence should be repeated until normal system operation is achieved.