24. Venting

Model LDAP heaters are certified as Category III heaters.

WARNING: Each heater requires its own individual vent pipe run and vent cap. Manifolding of vent runs can cause recirculation of combustion products into the building. Failure to comply could result in severe personal injury or death and/or property damage.

Venting must be in accordance with local codes and the National Fuel Gas Code Z223.1 or CSA B149.1 and B149.2, Installation Code for Gas Burning Appliances and Equipment. Local requirements supersede national requirements.

These power-vented heaters are designed to operate safely and efficiently with either a horizontal or vertical vent. Comply with the specific requirements and instructions.

If this heater is replacing an existing heater, be sure that the vent is sized properly for the heater being installed and that the existing vent is in good condition. A properly sized vent system is required for safe operation of the heater. An improperly sized vent system can cause unsafe conditions and/or create condensation. Do not vent into an existing gravity vent or chimney.

Installation should be done by a qualified agency in accordance with these instruc- tions. The qualified service agency installing this system is responsible for the instal- lation.

Venting Requirements

1) Type of Vent Pipe

The type of vent pipe is determined by whether the vent is horizontal or vertical.

Horizontal • Vent pipe approved for a Category III appliance, OR

2)Vent Pipe Diameter and Length

• Appropriately sealed 26-gauge or heavier galvanized

 

 

steel or equivalent single-wall pipe

Vertical

Vent pipe approved for a Category III appliance, OR

 

Appropriately sealed 26-gauge or heavier galvanized

 

 

steel or equivalent single-wall pipe

OR, if at least 75% of the equivalent length of the vent run is vertical

Double-wall (Type B) vent pipe

Vent pipe diameters and maximum vent lengths in the table apply to both Horizontal and Vertical vents. Add all straight sections and equivalent lengths for elbows. The total combined length must not exceed the Maximum Vent Length.

Use only one diameter of vent pipe on an installation.

Minimum vent length is 3 feet (1M).

Minimum of 1 ft (0.3M) of vertical vent required on venter outlet before installing an elbow.

Model

Venter

Vent Pipe

Maximum

Eqivalent

Equivalent

Field-Supplied Taper Type

Outlet

Vent Length

Straight Length

Straight Length

LDAP

Diameter

Connection Required at the Venter

Diameter

 

1

for 90° Elbow

for 45° Elbow

Size

 

 

 

 

Outlet

inches

mm

inches

mm

feet

M

feet

M

feet

M

 

 

400

6

152

6

152

45

13.7

15

4.6

7.5

2.3

None

7

178

60

18.3

8

2.4

4

1.2

6" to 7" (152 to 178mm) Increaser

 

 

 

800

8

203

8

203

50

15.2

15

4.6

7.5

2.3

None

10

254

45

13.7

5

1.5

2.5

0.8

8" to 10" (203 to 254mm) Increaser

 

 

 

1200

8

203

8

203

50

15.2

15

4.6

7.5

2.3

None

10

254

45

13.7

5

1.5

2.5

0.8

8" to 10" (203 to 254mm) Increaser

 

 

 

1 Includes one 90° elbow at venter outlet.

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 26

Page 26
Image 26
Thomas & Betts LDAP 1200 warranty Venting Requirements, Type of Vent Pipe, Vertical

LDAP 1200 specifications

The Thomas & Betts LDAP 1200 is a cutting-edge lighting control system designed specifically to enhance energy efficiency, reduce operational costs, and promote flexibility in various lighting applications. Ideal for commercial and industrial environments, the LDAP 1200 integrates advanced technologies to create a robust solution for managing lighting systems.

One of the standout features of the LDAP 1200 is its intelligent control capabilities. With occupancy sensors and daylight harvesting technology, the system can automatically adjust lighting levels based on the presence of people and the amount of natural light available. This results not only in energy savings but also in improved occupant comfort.

The LDAP 1200 is designed for easy installation and configuration. Its modular design allows for scalability, making it suitable for both small spaces and large commercial projects. The system supports a variety of lighting types, including LED, fluorescent, and incandescent, ensuring compatibility with existing infrastructure.

User-friendly interfaces are another key characteristic of the LDAP 1200. Operating through a centralized control panel or a mobile app, users can easily monitor and adjust lighting settings, schedule operations, and receive real-time feedback. This level of control empowers facility managers to respond quickly to changing needs and optimize lighting performance.

In terms of energy management, the LDAP 1200 integrates seamlessly with building management systems (BMS), enabling complex scheduling and reporting functions. The system collects data on energy usage, helping organizations to track performance and implement strategies to further reduce consumption.

Durability and reliability are paramount in industrial applications, and the LDAP 1200 does not disappoint. Constructed with high-quality materials, the system is designed to withstand everyday wear and tear. Its robust architecture ensures that it will function effectively in various environmental conditions.

In summary, the Thomas & Betts LDAP 1200 is a versatile and efficient lighting control solution that plays a critical role in enhancing energy efficiency, reducing costs, and improving user experience. With its intelligent control features, user-friendly interfaces, and compatibility with various lighting types, the LDAP 1200 represents a significant advancement in lighting technology, making it a smart choice for modern facilities seeking to optimize their lighting systems.