10.Heater Location (cont’d)

10.Heater Location (cont’d)

Sound Data

Sound Chart - Model LDAP

Model

 

 

 

 

 

 

 

 

DISTANCE

 

 

 

 

 

 

LDAP

 

20 ft (6.1M)

25 ft (7.6M)

30 ft (9.1M)

35 ft (10.7M)

40 ft (12.2M)

Size

db

 

Pa

µbar

db

 

Pa

µbar

db

Pa

µbar

db

Pa

µbar

db

Pa

µbar

400

69

 

0.058

0.580

65

 

0.037

0.371

62

0.026

0.258

60

0.019

0.189

57

0.015

0.145

800

72

 

0.080

0.800

68

 

0.051

0.512

65

0.036

0.356

62

0.026

0.261

60

0.020

0.200

1200

74

 

0.100

1.000

70

 

0.064

0.640

67

0.044

0.444

64

0.033

0.327

62

0.025

0.250

µbar =

microbar

Pa = Pascal

 

 

 

 

 

 

 

 

 

 

 

Location Recommendations

NOTE: Venting requirements may affect location. Consult requirements in Paragraph 24 before making final determination.

Hazards of Chlorine

For best results, the heater should be placed with certain rules in mind. In general, a heater should be located from 15-40 feet (4.6-12.2 M) above the floor. If two or more heaters are installed in the same room, a general scheme of air circulation should be maintained for best results.

Suspended heaters are most effective when located as close to the working zone as possible, and this fact should be kept in mind when determining the mounting heights to be used. However, care should be exercised to avoid directing the discharged air directly on the room occupants.

Partitions, columns, counters, or other obstructions should be taken into consider- ation when locating the heater so that a minimum quantity of airflow will be deflected by such obstacles.

The presence of chlorine vapors in the combustion air of gas-fired heating equipment presents a potential corrosion hazard. Chlorine found usually in the form of freon or degreaser vapors, when exposed to flame will precipitate from the compound, and go into solution with any condensation that is present in the heat exchanger or associated parts. The result is hydrochloric acid which readily attacks all metals including 300 grade stainless steel. Care should be taken to separate those vapors from the combus- tion process. This may be done by wise location of the heater with regard to exhaust- ers or prevailing wind directions. Chlorine is heavier than air. Keep these facts in mind when determining installation location of the heater in relation to building ex- haust systems.

11.Hanging or Mounting the Heater and Installing Louvers

Weight (lbs/kg)

Size

400

800

1200

Before installing the heater, check the supporting

lbs

375

805

1195

structure to be used to verify that it has sufficient load-

kg

170

365

542

carrying capacity to support the weight.

Suspending the Heater

Locate the hardware kit shipped with the heater. The kit contains spring nuts, hex nuts, “U”-shape fittings, and lock washers for suspending the heater. It also includes louvers and the compression springs needed to install them.

When the heater is lifted for suspension, support the bottom of the heater with the crate bottom. If the bottom is not supported, damage could occur. Before hanging or mounting, verify that any screws used for holding shipping brackets were re-installed in the cabinet.

WARNINGS: Check the supporting structure to be used to verify that it has sufficient load carrying capacity to support the weight of the heater. Suspend the heater only from the threaded nut retainers or with a manufacturer provided kit. Do NOT suspend from the heater cabinet.

See FIGURE 1A or 1B for the appropriate hanging locations, and install the ½”-13 spring nuts in the strut that is attached to the top of the unit. Comply with the require- ments in FIGURE 4A when using threaded rod. If ordered with swivel connectors for 1” pipe, Option CK10, attach the swivels to the spring nuts according to illustra- tion in FIGURE 4B and suspend with 1” pipe.

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 8