10.Heater Location (cont’d)
Sound Data
Sound Chart - Model LDAP
Model |
|
|
|
|
|
|
|
| DISTANCE |
|
|
|
|
|
| ||
LDAP |
| 20 ft (6.1M) | 25 ft (7.6M) | 30 ft (9.1M) | 35 ft (10.7M) | 40 ft (12.2M) | |||||||||||
Size | db |
| Pa | µbar | db |
| Pa | µbar | db | Pa | µbar | db | Pa | µbar | db | Pa | µbar |
400 | 69 |
| 0.058 | 0.580 | 65 |
| 0.037 | 0.371 | 62 | 0.026 | 0.258 | 60 | 0.019 | 0.189 | 57 | 0.015 | 0.145 |
800 | 72 |
| 0.080 | 0.800 | 68 |
| 0.051 | 0.512 | 65 | 0.036 | 0.356 | 62 | 0.026 | 0.261 | 60 | 0.020 | 0.200 |
1200 | 74 |
| 0.100 | 1.000 | 70 |
| 0.064 | 0.640 | 67 | 0.044 | 0.444 | 64 | 0.033 | 0.327 | 62 | 0.025 | 0.250 |
µbar = | microbar | Pa = Pascal |
|
|
|
|
|
|
|
|
|
|
|
Location Recommendations
NOTE: Venting requirements may affect location. Consult requirements in Paragraph 24 before making final determination.
Hazards of Chlorine
For best results, the heater should be placed with certain rules in mind. In general, a heater should be located from
Suspended heaters are most effective when located as close to the working zone as possible, and this fact should be kept in mind when determining the mounting heights to be used. However, care should be exercised to avoid directing the discharged air directly on the room occupants.
Partitions, columns, counters, or other obstructions should be taken into consider- ation when locating the heater so that a minimum quantity of airflow will be deflected by such obstacles.
The presence of chlorine vapors in the combustion air of
11.Hanging or Mounting the Heater and Installing Louvers
Weight (lbs/kg)
Size | 400 | 800 | 1200 | Before installing the heater, check the supporting |
lbs | 375 | 805 | 1195 | structure to be used to verify that it has sufficient load- |
kg | 170 | 365 | 542 | carrying capacity to support the weight. |
Suspending the Heater
Locate the hardware kit shipped with the heater. The kit contains spring nuts, hex nuts,
When the heater is lifted for suspension, support the bottom of the heater with the crate bottom. If the bottom is not supported, damage could occur. Before hanging or mounting, verify that any screws used for holding shipping brackets were
WARNINGS: Check the supporting structure to be used to verify that it has sufficient load carrying capacity to support the weight of the heater. Suspend the heater only from the threaded nut retainers or with a manufacturer provided kit. Do NOT suspend from the heater cabinet.
See FIGURE 1A or 1B for the appropriate hanging locations, and install the