Thomas & Betts UDAP Operating Gas Valve, Combustion Air Pressure Switch, Limit Control, UDAS only

Models: UDAP UDAS

1 36
Download 36 pages 48.13 Kb
Page 33
Image 33
FIGURE 22 - Venter Wheel Position on Shaft

FIGURE 22 - Venter Wheel Position on Shaft

5.Holding the venter motor, remove the three or four screws that attach the venter motor mounting plate to the venter housing. Remove the motor and wheel as- sembly from the heater.

6.Re-assemble with the replacement venter motor and wheel assembly. See FIG- URE 22.

7.Follow the wiring diagram to connect the venter wires.

8.Sizes 30 and 45 - Reconnect the gas supply at the union outside of the cabinet. Leak test the connection with leak detecting solution.

9.Replace the access panel. Restore power to the heater and turn on the gas. Light, following the instructions on the lighting instruction plate. Check for proper operation.

Venter Wheel,

 

Venter Motor Plate

 

Sizes 30-75

 

Fan

32.Operating Gas Valve Motor Mounting

Bracket

Motor Sizes 30-75

Venter Wheel, Sizes 100-175*

Single Venter Motor Plate

Fan

Optional Motor Mounting Bracket

Motor Sizes 100-400

*Venter wheel has different appearance on Sizes 200-400. Motor spacing is the same.

Stage33.Combustion Air Pressure Switch 5/16” (8mm) inside

34. Limit Control35. Door Switch 5/16” (8mm) inside

32.Operating Gas Valve

The gas valve requires no field maintenance except careful removal of external dirt accumulation and checking of wiring connections. Instructions for testing pressure settings re in Paragraph 12.

WARNING: The operating valve is the prime safety shutoff. All gas supply lines must be free of dirt or scale before connecting to the unit to ensure positive closure. See Hazard Levels, page 2.

Single

Optional

Stage

Two

Gas

Stage

Valve

Gas

 

Valve

33.Combustion Air Pressure Switch

See FIGURE 18, page 31, for location. If it is determined that the pressure switch needs replacing, use only the factory-autho- rized replacement part that is designed for the model and size of heater being serviced.

NOTE: A unit operating above 6000 ft elevation requires a high altitude pressure switch. See Paragraph 7.

34. Limit Control

If it is determined that the limit control needs replacing, use only a factory-authorized replacement part that is designed for the size of heater.

For approximate limit location, see FIGURE 18, page 31.

35. Door Switch

If it is determined that the door switch needs replacing, use only

a factory-authorized replacement part that is designed for the

- UDAS only

heater.

 

For approximate switch location, see FIGURE 18, page 31.

 

 

36. Transformer

See FIGURE 18, page 31, for location. Use a voltmeter to verify

that there are 24 volts output from the transformer. If the trans-

 

former is not functioning, it must be replaced. Use a replacement

 

transformer identical to the factory-installed model.

Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 33

Page 33
Image 33
Thomas & Betts UDAP Operating Gas Valve, Combustion Air Pressure Switch, Limit Control, Door Switch, UDAS only, Single