6. Technical Data

6. Technical Data

TECHNICAL DATA - Sizes 30 - 125 (Data applies to both Models UDAP and UDAS unless noted otherwise.)

Manual background Size

30

45

60

75

100

125

Input Heating Capacity

BTUH

30,000

45,000

60,000

75,000

105,000

120,000

kw

8.8

13.2

17.6

22.0

30.8

35.2

 

Thermal Efficiency (%)

 

82

83

83

83

83

83

Output Heating Capacity A

BTUH

24,600

37,350

49,800

62,250

87,150

99,600

kw

7.2

11.0

14.6

18.3

25.6

29.2

 

Gas Connection (inches) B

Natural

1/2

1/2

1/2

1/2

1/2

1/2

Propane

1/2

1/2

1/2

1/2

1/2

1/2

 

Vent Connection C (inches diameter)

 

4

4

4

4

4

4

Combustion Air Inlet C (inches diameter) - UDAS only

4

4

4

4

4

4

Control Amps (24 volt)

 

1.0

1.0

1.0

1.0

1.0

1.0

Full Load Amps (115 volt)

 

1.9

2.4

2.4

3.3

3.9

5.1

Maximum Over Current Protection (115V) D

15

15

15

15

15

15

Normal Power Consumption (watts)

 

109

155

155

217

276

354

Discharge Air Temperature Rise (°F)

 

50

55

60

60

60

60

Air Volume

CFM

456

629

769

961

1345

1537

M3/minute

12.9

17.8

21.8

27.5

36.7

45.9

 

Discharge Air Opening Area

ft2

0.96

0.96

1.25

1.25

2.01

2.01

M2

0.09

0.09

0.12

0.12

0.19

0.19

 

Output Velocity

FPM

475

656

616

770

668

763

M/minute

145

200

188

238

196

245

 

Fan Motor HP E

Open

0.02

0.03

0.03

0.06

1/30

1/20

Enclosed

N.A.

N.A.

N.A.

N.A.

1/4

1/4

 

Fan Motor RPM

 

1550

1550

1550

1550

1050

1050

Fan Diameter (inches)

 

10

10

12

12

16

16

Sound Level

dba @ 15 ft

40

40

40

49

54

55

TECHNICAL DATA - Sizes 150 - 400 (Data applies to both Models UDAP and UDAS unless noted otherwise.)

Size

 

150

175

200

225

250

300

350

400

Input Heating Capacity

BTUH

150,000

175,000

200,000

225,000

250,000

300,000

350,000

400,000

kw

43.9

51.2

58.6

65.9

73.2

87.8

102.5

117.1

 

Thermal Efficiency (%)

 

83

83

83

83

83

83

83

83

Output Heating Capacity A

BTUH

124,500

145,250

166,000

186,750

207,500

249,000

290,500

332,000

kw

36.4

42.5

48.6

54.7

60.8

72.9

85.1

97.2

 

Gas Connection (inches) B

Natural

1/2

1/2

1/2

3/4

3/4

3/4

3/4

3/4

Propane

1/2

1/2

1/2

3/4

3/4

3/4

3/4

3/4

 

Vent Connection C (inches diameter)

 

5

5

5

5

5

6

6

6

Combustion Air Inlet C (inches diameter) - UDAS only

6

6

6

6

6

6

6

6

Control Amps (24 volt)

 

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Full Load Amps (115 volt)

 

3.8

3.8

4.6

7.5

7.5

10.7

10.7

10.7

Maximum Over Current Protection (115V) D

15

15

15

15

15

20

20

20

Normal Power Consumption (watts)

 

392

392

491

747

747

1086

1086

1086

Discharge Air Temperature Rise (°F)

 

60

60

60

60

60

60

60

60

Air Volume

CFM

1921

2242

2562

2882

3202

3843

4483

5123

M3/minute

54.4

63.5

72.5

81.6

90.7

108.8

126.9

145.1

 

Discharge Air Opening Area

ft2

2.56

2.56

2.56

3.51

3.51

4.79

4.79

4.79

M2

0.24

0.24

0.24

0.33

0.33

0.45

0.45

0.45

 

Output Velocity

FPM

752

877

1003

820

911

802

936

1069

M/minute

229

267

306

250

278

244

285

326

 

Fan Motor HP E

Open

1/6

1/6

1/6

1/4

1/4

1/2

1/2

1/2

Enclosed

1/4

1/4

1/4

1/4

1/4

1/2

1/2

1/2

 

Fan Motor RPM

 

1050

1050

1050

1050

1050

1050

1050

1050

Fan Diameter (inches)

 

18

18

18

20

20

24

24

24

Sound Level

dba @ 15 ft

51

52

53

56

56

59

61

62

A CSA ratings for altitudes to 2000 ft.

 

B Size shown

is for gas

connection to

a single-stage

gas valve, not supply line size.

 

CSmaller and/or larger vent and combustion air pipe diameters may be permissible. For Model UDAS refer to the Venting Installation Manual for Separated Combustion Units. For Model UDAP refer to the Venting Installation Manual for Power Vented units. For a Model UDAP with Option AV6, refer to the Venting Installation Manual for Common Venting.

DMOCP = 2.25 x (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.

EAll other information is this table is based on a heater equipped with a standard 115 volt open fan motor.

Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 6