Thomas & Betts UDAP, UDAS dimensions Unit Heater Location, Heater Throw, Location Recommendations

Models: UDAP UDAS

1 36
Download 36 pages 48.13 Kb
Page 9
Image 9
10.Unit Heater Location

10.Unit Heater Location

Use the sound data in Paragraph 6, clearances in Paragraph 8; the combustion air requirements in Paragraph 9; the throw tables, mounting height requirements, and location recommendations below; the weights in Paragraph 11; and the venting requirements in the Venting Manual to determine where to suspend the heater.

Heater Throw

FIGURE 6 - Throw for Fan Models UDAP and UDAS

NOTE: Throws listed are with standard adjustable horizontal louvers at the angles listed (angle is relative to the top of the heater). Throw pattern changes with the addition of optional vertical louvers and/or downturn nozzles.

H

*Louver angle listed in the table is relative to the top of the heater.

 

 

X

 

 

 

 

 

 

 

 

 

 

**“Z” is the point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

 

 

 

 

 

 

when the air velocity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

drops below 50 feet

 

 

 

 

 

 

 

 

 

 

 

 

 

Z**

 

 

 

 

 

 

 

 

 

 

 

 

(15.2M) per minute.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions X, Y, and Z (feet) Model UDAP and Model UDAS with Standard Horizontal Louvers at Mounting Heights of 5 - 18 ft

 

 

 

30

 

 

 

45

 

 

 

60

 

 

 

75

 

 

 

100

 

 

 

125

 

 

 

 

 

 

 

 

 

 

H

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 ft

6

14

 

30

-21°

7

16

 

40

-20°

8

18

 

45

-16°

9

20

 

57

-14°

9

20

 

59

-18°

10

22

 

65

-14°

 

 

 

 

 

 

 

 

 

8 ft

7

13

 

26

-39°

9

16

 

37

-34°

10

18

 

42

-29°

12

22

 

54

-25°

11

21

 

56

-28°

12

23

 

63

-24°

 

 

 

 

 

 

 

 

 

10 ft

6

11

 

22

-52°

9

15

 

33

-43°

10

17

 

39

-37°

12

22

 

52

-32°

12

20

 

52

-36°

13

24

 

60

-30°

 

 

 

 

 

 

 

 

 

12 ft

-

-

 

-

-

8

12

 

27

-55°

10

16

 

34

-46°

12

21

 

48

-39°

11

19

 

47

-44°

14

23

 

57

-36°

 

 

 

 

 

 

 

 

 

14 ft

-

-

 

-

-

-

-

 

-

-

9

14

 

29

-56°

12

19

 

44

-46°

11

17

 

42

-51°

14

22

 

53

-43°

 

 

 

 

 

 

 

 

 

16 ft

-

-

 

-

-

-

-

 

-

-

-

-

 

-

-

11

17

 

38

-54°

10

14

 

34

-58°

13

20

 

47

-50°

 

 

 

 

 

 

 

 

 

18 ft

-

-

 

-

-

-

-

 

-

-

-

-

 

-

-

-

-

 

-

-

-

-

 

-

-

11

17

 

40

-57°

 

 

 

 

 

 

 

 

 

 

 

150

 

 

175

 

 

200

 

 

225

 

 

 

250

 

 

 

300

 

 

 

350

 

 

400

 

H

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

 

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8 ft

13

24

 

73

-26°

15

28

 

90

-22°

16

30

 

93

-20°

14

27

 

86

-24°

16

29

 

93

-21°

15

28

 

94

-24°

17

31

105

-20°

18

34

113

-17°

10 ft

14

24

 

69

-32°

17

29

 

87

-27°

17

31

 

91

-25°

15

27

 

82

-30°

17

30

 

90

-26°

16

28

 

89

-29°

18

32

103

-25°

20

35

110

-21°

12 ft

14

24

 

64

-39°

18

29

 

84

-32°

18

31

 

88

-30°

16

27

 

78

-35°

18

30

 

87

-31°

17

28

 

85

-34°

19

32

98

-30°

21

36

108

-25°

14 ft

14

22

 

59

-45°

18

28

 

79

-37°

19

30

 

84

-34°

16

26

 

73

-41°

18

30

 

83

-36°

17

27

 

80

-40°

20

32

95

-34°

23

35

105

-29°

16 ft

13

20

 

53

-51°

18

27

 

74

-42°

19

29

 

79

-39°

16

24

 

67

-47°

19

28

 

78

-41°

17

25

 

74

-45°

21

31

90

-38°

23

35

101

-33°

18 ft

11

17

 

44

-58°

17

26

 

68

-48°

19

28

 

74

-44°

14

22

 

60

-53°

18

27

 

72

-46°

16

24

 

66

-51°

20

30

85

-43°

23

35

97

-37°

Dimensions X, Y, and Z (meters) Model UDAP and Model UDAS with Standard Horizontal Louvers at Mounting Heights of 1.5 - 5.5M

 

 

 

30

 

 

 

45

 

 

 

60

 

 

 

75

 

 

100

 

 

125

 

 

 

 

 

 

 

 

 

 

H

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5 M

1.8

4.3

 

9.1

-21°

2.1

4.9

 

12.2

-20°

2.4

5.5

 

13.8

-16°

2.7

6.1

 

17.4

-14°

2.7

6.1

18.0

-18°

3.0

6.7

19.9

-14°

 

 

 

 

 

 

 

 

 

2.4 M

2.1

4.0

 

7.9

-39°

2.7

4.9

 

11.3

-34°

3.0

5.5

 

12.8

-29°

3.7

6.7

 

16.5

-25°

3.4

6.4

17.1

-28°

3.7

7.0

19.2

-24°

 

 

 

 

 

 

 

 

 

3.0 M

1.8

3.4

 

6.7

-52°

2.7

4.6

 

10.0

-43°

3.0

5.2

 

11.9

-37°

3.7

6.7

 

15.8

-32°

3.7

6.1

15.8

-36°

4.0

7.3

18.3

-30°

 

 

 

 

 

 

 

 

 

3.7 M

-

-

 

-

-

2.4

3.7

 

8.2

-55°

3.0

4.9

 

10.4

-46°

3.7

6.4

 

14.6

-39°

3.4

5.8

14.3

-44°

4.3

7.0

17.4

-36°

 

 

 

 

 

 

 

 

 

4.3 M

-

-

 

-

-

-

-

 

-

-

2.7

4.3

 

8.8

-56°

3.7

5.8

 

13.4

-46°

3.4

5.2

12.8

-51°

4.3

6.7

16.1

-43°

 

 

 

 

 

 

 

 

 

4.9 M

-

-

 

-

-

-

-

 

-

-

-

-

 

-

-

3.4

5.2

 

11.6

-54°

3.0

4.3

10.4

-58°

4.0

6.1

14.3

-50°

 

 

 

 

 

 

 

 

 

5.5 M

-

-

 

-

-

-

-

 

-

-

-

-

 

-

-

-

-

 

-

-

-

-

-

-

3.4

5.2

12.2

-57°

 

 

 

 

 

 

 

 

 

 

 

150

 

 

175

 

 

200

 

 

225

 

 

250

 

 

300

 

 

 

350

 

 

400

 

H

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

 

X

Y

Z

Louver Angle*

X

Y

Z

Louver Angle*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.4 M

4.0

7.3

 

22.3

-26°

4.6

8.5

 

27.4

-22°

4.9

9.1

 

28.0

-20°

4.3

8.2

 

26.2

-24°

4.9

8.8

28.3

-21°

4.6

8.5

28.7

-24°

5.2

9.4

32.0

-20°

5.5

11.3

34.4

-17°

3.0 M

4.3

7.3

 

21.0

-32°

5.2

8.8

 

26.6

-27°

5.2

9.4

 

27.7

-25°

4.6

8.2

 

25.0

-30°

5.2

9.1

27.4

-26°

4.9

8.5

27.1

-29°

5.5

9.8

31.4

-25°

6.1

10.7

33.5

-21°

3.7 M

4.3

7.3

 

19.5

-39°

5.5

8.8

 

25.6

-32°

5.5

9.4

 

26.8

-30°

4.9

8.2

 

23.8

-35°

5.5

9.1

26.5

-31°

5.2

8.5

25.9

-34°

5.8

9.8

29.9

-30°

6.4

11.0

32.9

-25°

4.3 M

4.3

6.7

 

18.0

-45°

5.5

8.5

 

24.1

-37°

5.8

9.1

 

25.6

-34°

4.9

7.9

 

22.3

-41°

5.5

9.1

25.3

-36°

5.2

8.2

24.4

-40°

6.1

9.8

29.0

-34°

7.0

10.7

32.0

-29°

4.9 M

4.0

6.1

 

16.2

-51°

5.5

8.2

 

22.6

-42°

5.8

8.8

 

24.1

-39°

4.9

7.3

 

20.4

-47°

5.8

8.5

23.8

-41°

5.2

7.6

22.6

-45°

6.4

9.4

27.4

-38°

7.0

10.7

30.8

-33°

5.5 M

3.4

5.2

 

13.4

-58°

5.2

7.9

 

20.7

-48°

5.8

8.5

 

22.6

-44°

4.3

6.7

 

18.3

-53°

5.5

8.2

21.9

-46°

4.9

7.3

20.1

-51°

6.1

9.1

25.9

-43°

7.0

10.7

26.9

-37°

Location Recommendations

Locate the heater so that it is a minimum of five feet (1.5M) above the floor and in compliance with the clearances in Paragraph 8.

WARNING: If touched, the vent pipe and internal heater surfaces that are accessible from outside the heater will cause burns. Suspend the heater a minimum of 5 feet (1.5M) above the floor.

Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 9

Page 9
Image 9
Thomas & Betts Unit Heater Location, Heater Throw, Location Recommendations, Throw for Fan Models UDAP and UDAS