Thomas & Betts UDAS Flame Rollout Switch - Sizes 30-125 only, Disconnect, Vent or Vent, Flowchart

Models: UDAP UDAS

1 36
Download 36 pages 48.13 Kb
Page 34
Image 34
37.Flame Rollout Switch - Sizes 30-125 only
• Restricted combustion air inlet or exhaust outlet in combination with a defective pressure switch
• Building exhaust
• Electrical power interruption during operation

37.Flame Rollout Switch - Sizes 30-125 only

For location, see FIGURE 18, page 31.

The cause of a flame rollout switch activating must be determined. Activation of the manually reset flame rollout switch could be caused by one or more of the following:

• Restricted or plugged heat exchanger

• Pressurization of the heat exchanger

If a flame rollout switch trips, inspect the burner/control compartment for signs of excessive heat and burned wiring.

If the compartment appears normal, reset by depressing the red button on the switch. 15 to 20 minutes are required for the switch to cool sufficiently for reset- ting. A distinct click will be felt when the switch resets. Operate the furnace. If the flame rollout switch trips again, determine and correct the cause before reset- ting the switch.

If there is damage to the control compartment, repairs must be made before

resetting the switch.

If it is determined that the flame rollout switch needs replacing, use only the fac- tory-authorized replacement part that is designed for that size of heater.

38. Disconnect

The disconnect switch is located in the sealed electrical box inside the con-

trol compartment with the toggle on the rear of the heater.

Switch -

If it is determined that the disconnect switch needs replacing, use only the

UDAS only

factory-authorized replacement part that is designed for the heater. Always

replace electrical box cover.

 

 

 

 

39. Vent or Vent/

Check the complete system at least once a year. Inspection should include all joints,

Combustion

seams, concentric adapter box (UDAS), inlet air guard or inlet air cap (UDAS), and

the vent terminal cap. Clean openings. Replace any defective parts.

Air System

 

 

40. Troubleshooting

DSI Integrated Control Module

Trial for Ignition

 

 

Call for Heat

 

 

 

 

 

(Circuit Board) Trial

 

 

 

 

 

 

 

Is there a

NO

 

YES

spark across gap at

 

Troubleshooting

 

 

ignitor?

 

 

 

 

 

Flowchart

 

 

Is there

YES

YES Does gas NO

 

 

spark voltage at

ignite?

 

 

 

 

 

control?

 

 

 

 

 

 

 

 

NO

 

Check high voltage wire continuity.

YES

Is there minimum

NO

Is the flame

YES

Clean flame

flame current at the

sensor corroded?

 

 

 

sensor.

 

flame sensor?

 

 

 

 

 

 

 

 

NO

Is there 24V P1-2

YES

to power control?

 

NO

 

Replace control module.

Is there

minimum flame current YES at the control

module?

NO

Replace control

module.

Is the sensor

YES

Replace flame

located in flame

 

sesnsor.

correctly?

 

 

 

NO

Check wiring

and/or 24VAC

transformer output.

Check connections to flame sensor and/or moisture in the burner assembly.

Reposition

flame sensor.

Check gas pressure and supply voltage.

YES

YES

Is the ignitor

Is gas

NO

 

flowing?

 

 

Replace gas

YES

Is there

 

If either are low, correct and repeat startup.

position correct in the

gas flow?

NO

Reposition

spark ignitor.

 

valve.

 

24VAC at the gas

 

 

 

valve?

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

Is there 24VAC

 

Check wiring and

YES

NO

from gas valve output on

 

connections to

 

 

control module to

 

 

gas valve.

 

 

 

 

chassis?

 

 

 

 

 

 

Replace ignition control module.

Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 34

Page 34
Image 34
Thomas & Betts UDAS Flame Rollout Switch - Sizes 30-125 only, Disconnect, Vent or Vent, Combustion, Air System, Flowchart