37.Flame Rollout Switch - Sizes 30-125 only
For location, see FIGURE 18, page 31.
The cause of a flame rollout switch activating must be determined. Activation of the manually reset flame rollout switch could be caused by one or more of the following:
• Restricted or plugged heat exchanger
• Pressurization of the heat exchanger
If a flame rollout switch trips, inspect the burner/control compartment for signs of excessive heat and burned wiring.
If the compartment appears normal, reset by depressing the red button on the switch. 15 to 20 minutes are required for the switch to cool sufficiently for reset- ting. A distinct click will be felt when the switch resets. Operate the furnace. If the flame rollout switch trips again, determine and correct the cause before reset- ting the switch.
If there is damage to the control compartment, repairs must be made before
resetting the switch.
If it is determined that the flame rollout switch needs replacing, use only the fac-
38. Disconnect | The disconnect switch is located in the sealed electrical box inside the con- | ||
trol compartment with the toggle on the rear of the heater. | |||
Switch - | |||
If it is determined that the disconnect switch needs replacing, use only the | |||
UDAS only | |||
replace electrical box cover. | |||
| |||
|
|
| |
39. Vent or Vent/ | Check the complete system at least once a year. Inspection should include all joints, | ||
Combustion | seams, concentric adapter box (UDAS), inlet air guard or inlet air cap (UDAS), and | ||
the vent terminal cap. Clean openings. Replace any defective parts. | |||
Air System |
|
|
40. Troubleshooting
DSI Integrated Control Module | Trial for Ignition |
|
| |
Call for Heat |
|
| ||
|
|
| ||
(Circuit Board) Trial |
|
|
| |
|
|
|
| |
Is there a | NO |
| ||
YES | spark across gap at |
| ||
Troubleshooting |
|
| ||
ignitor? |
|
| ||
|
|
| ||
Flowchart |
|
| Is there | YES |
YES Does gas NO |
|
| spark voltage at | |
ignite? |
|
|
| |
|
| control? |
| |
|
|
|
| |
|
|
| NO |
|
Check high voltage wire continuity.
YES | Is there minimum | NO | Is the flame | YES | Clean flame | |
flame current at the | sensor corroded? | |||||
|
|
| sensor. | |||
| flame sensor? |
|
|
| ||
|
|
|
|
|
NO
Is there 24V | YES |
to power control? |
|
NO |
|
Replace control module.
Is there
minimum flame current YES at the control
module?
NO
Replace control
module.
Is the sensor | YES | Replace flame | |
located in flame | |||
| sesnsor. | ||
correctly? |
| ||
|
|
NO
Check wiring |
and/or 24VAC |
transformer output. |
Check connections to flame sensor and/or moisture in the burner assembly.
Reposition
flame sensor.
Check gas pressure and supply voltage.
YES
YES
Is the ignitor
Is gas | NO |
|
flowing? |
|
|
Replace gas | YES | Is there |
|
If either are low, correct and repeat startup.
position correct in the
gas flow?
NO
Reposition
spark ignitor.
| valve. |
| 24VAC at the gas |
| ||
|
| valve? |
| |||
|
|
|
|
| ||
|
|
|
| NO |
| |
|
|
|
| Is there 24VAC |
| |
Check wiring and | YES | NO | ||||
from gas valve output on | ||||||
| connections to | |||||
|
| control module to |
| |||
| gas valve. |
|
| |||
|
| chassis? |
| |||
|
|
|
|
|
Replace ignition control module.
Form