Thomas & Betts UDAS, UDAP dimensions Combustion Air Proving, Limit Control, Switch cont’d

Models: UDAP UDAS

1 36
Download 36 pages 48.13 Kb
Page 18
Image 18
16.Combustion Air Proving

16.Combustion Air Proving

Switch (cont’d)

Pressure Switch Settings

The two Tables on the left below list the approximate water column negative pres- sure readings and switch setpoints for sea level operating conditions for Model UDAP and Model UDAP-CV heaters. The Table on the right lists the approximate water column differential pressure readings and switch setpoints for sea level op- erating conditions for Model UDAS heaters.

DANGER: Safe operation of this unit requires proper venting flow. NEVER bypass combustion air proving switch or attempt to operate the unit without the venter running and the proper flow in the vent system. Hazardous conditions could result. See Hazard Levels, page 2.

Model

Startup

Equilibrium

Setpoint

Setpoint

Label

Switch

Cold

Hot

OFF

ON

UDAP

Color

P/N

Negative Pressure Measured in " w.c.

 

 

 

30

1.00

0.78

0.40

0.58

Green

197030

45

0.95

0.75

0.40

0.58

Green

197030

60

1.00

0.78

0.50

0.68

Orange

196388

75

1.00

0.85

0.50

0.68

Orange

196388

100

0.85

0.72

0.50

0.68

Orange

196388

125

0.75

0.60

0.40

0.58

Green

197030

150, 175

0.75

0.65

0.40

0.58

Green

197030

200, 225

2.20

1.50

1.10

1.30

Blue

201158

250, 300

2.30

1.60

1.10

1.30

Blue

201158

350, 400

2.60

1.80

1.40

1.60

Red

201159

Model

Startup

Equilibrium

Setpoint

Setpoint

Label

Switch

UDAS

Cold

Hot

OFF

ON

Color

P/N

Differential Pressure Measured in " w.c.

 

 

 

30

1.00

0.78

0.65

0.83

Yellow

197028

45

1.05

0.80

0.65

0.83

Yellow

197028

60

1.10

0.85

0.65

0.83

Yellow

197028

75

1.10

0.85

0.65

0.83

Yellow

197028

100

0.85

0.72

0.55

0.73

White

196362

125

0.75

0.60

0.45

0.63

Pink

197032

150, 175

0.75

0.60

0.40

0.58

Green

197030

200, 225

2.20

1.50

1.10

1.30

Blue

201158

250, 300

2.30

1.60

1.10

1.30

Blue

201158

350, 400

2.60

1.80

1.40

1.60

Red

201159

Model UDAP-CV

Startup

Equilibrium

Setpoint

Setpoint

Label

Switch

Cold

Hot

OFF

ON

with Opt AV6

Color

P/N

Negative Pressure Measured in " w.c.

 

 

 

30

1.10

0.84

0.65

0.83

Yellow

197028

45

1.10

0.81

0.50

0.68

Orange

196388

60

0.92

0.75

0.60

0.78

Lt Blue

197029

75

0.97

0.78

0.60

0.78

Lt Blue

197029

100

0.88

0.71

0.55

0.73

White

196362

17. Limit Control

All units are equipped with a temperature activated auto reset limit control. The

 

control is factory set and is non-adjustable. If the setpoint is reached, the limit

 

control will interrupt the electric supply to the gas valve. This safety device pro-

 

vides protection in the case of motor failure or lack of airflow due to a restriction at

 

the inlet or outlet. (For location, see FIGURE 18, page 31.)

18.Flame Rollout Switch - Sizes 30-125only

CAUTION: The auto reset limit control will continue to shut down the heater until the cause is corrected. Never bypass the limit control; hazardous conditions could result. See Hazard Intensity Levels, page 2.

Sizes 30-125 are equipped with a temperature activated manually reset flame rollout switch. The flame rollout switch is located at the top of the burner assembly. It is factory set and is non-adjustable. If the setpoint is reached, the flame rollout acts to interrupt the electric supply to the gas valve. If the flame rollout switch activates, identify and correct the cause before resetting the switch. Refer to the Mainte- nance Section for information on probable causes and instructions on resetting the flame rollout switch. (For location, see FIGURE 18, page 31.)

DANGER: If the manual reset flame rollout switch activates, identify and correct the cause before resetting the switch. Never bypass the flame rollout switch; hazardous conditions could result. See Hazard Intensity Levels, page 2.

Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 18

Page 18
Image 18
Thomas & Betts UDAS, UDAP Combustion Air Proving, Limit Control, Flame Rollout Switch - Sizes 30-125 only, Switch cont’d