19.Door Switch - Model UDAS only

19.Door Switch - Model UDAS only

20.Ignition System

All sizes of Model UDAS heaters are equipped with a door switch which prevents the heater from operating when the service door panel is open. The service panel of a Model UDAS is equipped with a pliable gasket material that fully seals the door to provide added protection from building air entering the combustion zone of the heater. (For switch location, see FIGURE 18, page 31.)

This heater is equipped with a direct spark integrated control module (circuit board). The module monitors the safety devices and controls the operation of the fan and venter motors and the gas valve between heat cycles.

FIGURE 14 – DSI Integrated Control Module (circuit board)

 

x

Spark

 

Transformer

Control Plug

 

Fuse

Thermostat

Connections

Dip Switch

Fan/Blower

Off

Delay

StatusLED Lights

Lights

Flame Status - Yellow LED Codes

Control Status - Green LED Codes

Steady ON

Normal Operation, No call for heat

Fast Flash

Normal Operation, Call for heat

1

Flash

System Lockout, Failed to detect or sustain

 

 

flame

2

Flashes

Pressure Switch Did Not Close within 30

 

 

Seconds of Venter Motor

3

Flashes

High Limit or Flame Rollout Switch Open

4 Flashes

Pressure switch is closed before venter

 

 

motor is energized

Steady OFF

Blown Fuse, No Power, or Defective Board

Steady ON

Flame is sensed

Slow Flash

Weak flame (current below 1.0

 

microamps ±50%)

Fast Flash

Undesired Flame (valve open

 

and no call for heat)

Fan/Blower OFF Delay Settings (dip switches)

SW-1 SW-2 Time

Off

Off

120 seconds (factory setting)

Off

On

90 seconds

On

Off

160 seconds

On

On

180 seconds

Normal Heat Cycle

Operating

Sequence

1)Call for Heat - The thermostat calls for heat by energizing the “W” terminal. The control checks to see that the limit switch is closed and the pressure switch is open. If the limit switch is open, the control responds as defined in the “Abnormal Heat Cycle, Limit Switch Operation”. If the pressure switch is closed, the control will do four flashes on the green LED and wait indefinitely for the pressure switch to open. If the pressure switch is open, the control proceeds to prepurge.

2)Prepurge - The control energizes the venter motor and waits for the pressure switch to close. If the pressure switch does not close within 30 seconds of the venter motor energizing, the control will do two flashes on the green LED. The control will leave the venter motor energized indefinitely as long as the call for heat remains and the pressure switch is open.

Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 19