7.High Altitude Operation
Gas valve adjustment for high altitude can only be done after heater is operating; see Paragraph 12.
If the heater is being installed at an elevation above 2000 ft (610M), the input rate will have to be derated. This is done by adjusting the valve outlet pressure.
In addition, if the heater is being installed at an altitude above 6000 ft (1830M), the pressure switch will have to be changed. If ordered with the unit as Option DJ20 or DJ21, the pressure switch is shipped separately.
Adjusting the valve outlet pressure is done after the heater is in operation; follow the instructions in Paragraph 12. Capacities and inputs for derated units are also listed in Paragraph 12.
If the pressure switch needs to be changed, do that before the heater is operated; follow the instructions in FIGURE 4.
FIGURE 4 - Installing High Altitude Pressure Switch required above 6000 ft (1830M) elevation
Model UDAP
Size | 30 | 45 |
| 60 | 75 | 100 | 125 |
| 150 | 175 | 200 | 225 | 250 | 300 | 350 | 400 | |
High Altitude Switch P/N | 197031 |
|
| 197032 | 197031 |
|
| 201160 |
| 201161 | |||||||
Negative Pressure OFF Setpoint "w.c. | 0.35 |
|
| 0.45 |
|
| 0.35 |
|
| 1.00 |
| 1.30 | |||||
Label color | Purple |
|
| Pink |
| Purple |
|
| Brown |
| White | ||||||
Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Size | 30 | 45 |
| 60 | 75 | 100 |
|
|
|
|
|
|
|
|
|
|
|
High Altitude Switch P/N | 197029 | 197032 |
| 196362 | 196388 |
|
|
|
|
|
|
|
|
|
|
| |
Negative Pressure OFF Setpoint "w.c. | 0.60 | 0.45 |
| 0.55 | 0.50 |
|
|
|
|
|
|
|
|
|
|
| |
Label color | Lt Blue | Pink |
| White | Orange |
|
|
|
|
|
|
|
|
|
|
| |
Model UDAS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Size | 30 | 45 |
| 60 | 75 | 100 | 125 |
| 150 | 175 | 200 | 225 | 250 | 300 | 350 | 400 | |
High Altitude Switch P/N |
| 197029 |
|
|
| 196388 | 197030 |
| 197031 |
| 201160 |
| 201161 | ||||
Differential Pressure OFF Setpoint "w.c. |
| 0.60 |
|
|
| 0.50 | 0.40 |
| 0.35 |
| 1.00 |
| 1.30 | ||||
Label color |
| Lt. Blue |
|
| Orange |
| Green |
| Purple |
| Brown |
| White |
Instructions for Changing Pressure Switch
1. | In the control compartment, locate the pressure switch. |
| Sizes |
| Sizes |
2. | Mark and disconnect the two wires attached to the pressure switch. |
3. | Disconnect the sensing tube from the pressure switch. |
4. | Locate the two screws holding the switch mounting bracket. Remove the |
Pressure Switch | screws (save screws) and the pressure switch. |
5. | Using the same screws, install the high altitude pressure switch. Attach the |
| sensing tube and wires. |
8. Clearances
Units must be installed so that the clearances in the table are provided for combus- tion air space, inspection and service, and for proper spacing from combustible construction. Clearance to combustibles is defined as the minimum distance from the heater to a surface or object that is necessary to ensure that a surface tempera- ture of 90°F above the surrounding ambient temperature is not exceeded.
Clearances
Size | Top | Flue Connector | Access Panel | Bottom* | Rear | ||||||||
inches | mm | inches | mm | inches | mm | inches | mm | inches | mm | inches | mm | ||
| |||||||||||||
1 | 25 | 6 | 152 | 18 | 457 | 1 | 25 | 1 | 25 | 18 | 457 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
4 | 102 | 6 | 152 | 18 | 457 | 2 | 51 | 1 | 25 | 18 | 457 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
*Suspend the heater so that the bottom is a minimum of 5 feet (1.5M) above the floor.
Form