ICC

BO4...... Resets the drive when it is faulted. ASD parameter FA06, bit#13.

BO5...... Enables or disables process (PID) feedback control. Note that this

object does not activate (turn on) feedback control. It only enables or disables feedback control once it has already been activated. ASD parameter FA06, bit#5.

BO6...... Communication interface frequency priority selection. Allows the

frequency command from the interface card to be used by the drive without having to set the Frequency Mode parameter. Refer to the Toshiba documentation regarding "Command Mode and Frequency Mode Control" for detailed information pertaining to the frequency source hierarchy and the use of overrides. ASD parameter FA06, bit#14.

BO7...... Communication interface command priority selection. Allows

commands (BO1, BO2, and BO5) from the interface card to be used by the drive without having to explicitly set the Command Mode parameter. Refer to the Toshiba documentation regarding "Command Mode and Frequency Mode Control" for detailed information pertaining to the command source hierarchy and the use of overrides. ASD parameter FA06, bit#5.

BO8...... Output terminal data out 1. Any programmable output terminals that

are configured to output “specified data output 1” will follow the value of this BO. ASD parameter FA50, bit#0.

BO9...... Output terminal data out 2. Any programmable output terminals that

are configured to output “specified data output 2” will follow the value of this BO. ASD parameter FA50, bit#1.

BO10 .... Output terminal data out 3. Any programmable output terminals that

are configured to output “specified data output 3” will follow the value of this BO. ASD parameter FA50, bit#2.

Analog Input Objects

AI1........ Output frequency in 0.01Hz units. ASD parameter FD00.

AI2........ Load current in 0.01% units (10000=100.00%=drive's rated current).

ASD parameter FE03.

AI3........ Output voltage in 0.01% units (10000=100.00%=drive's rated voltage).

ASD parameter FE05.

AI4........ Input power consumption (drive+motor) in 0.01kW units. ASD

parameter FE29.

AI5........ Indicates the signal level currently being applied to the ASD's RR

analog input terminal. This can be used to monitor such items as feedback sensor outputs and other process variables. Expressed in 0.01% units (10000=100.00%=input rated value). ASD parameter FE35.

102