ICC

Binary Output Object Instance Summary

Instance

 

Object Name

 

Description

 

 

Active/

 

ID

 

 

 

 

Inactive Text

 

 

 

 

 

 

 

 

 

BO1

RUN_STOP_CMD

Run/stop command

 

 

run/stop

 

BO2

FWD_REV_SEL

Forward/reverse

 

reverse/forward

 

command

 

 

 

 

 

 

 

 

 

 

BO3

EMERGENCY_OFF

Emergency off

 

 

emergency off/

 

command

 

 

no action

 

 

 

 

 

 

 

BO4

FAULT_RESET

Fault reset command

 

 

reset/no action

 

BO5

FEEDBACK_CTRL_SEL

Feedback enable/

 

 

enable/disable

 

 

 

 

disable selection

 

 

 

 

 

BO6

FREQ_PRIORITY

Frequency priority

 

 

 

on/off

 

BO7

COMMAND_PRIORITY

Command priority

 

 

 

on/off

 

BO8

DATA_OUT1_TERMINAL

Output terminal

 

 

 

on/off

 

 

 

 

“selected data out 1”

 

 

 

 

 

BO9

DATA_OUT2_TERMINAL

Output terminal

 

 

 

on/off

 

 

 

 

“selected data out 2”

 

 

 

 

 

BO10

DATA_OUT3_TERMINAL

Output terminal

 

 

 

on/off

 

 

 

 

“selected data out 3”

 

 

 

 

 

Analog Input Object Instance Summary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instance ID

Object Name

 

 

Description

 

Units

 

AI1

 

OUTPUT_FREQ

 

 

Output frequency

 

Hz

 

AI2

 

LOAD_CURRENT

 

 

Output current

 

 

Percent

 

AI3

 

OUTPUT_VOLTAGE

 

 

Output voltage

 

 

Percent

 

AI4

 

INPUT_POWER_CONSUME

Input power

 

 

KW

 

AI5

 

RR_ANALOG_INPUT

 

 

RR/S4 input

 

 

Percent

 

AI6

 

VI_II_ANALOG_INPUT

 

 

VI/II input

 

 

Percent

 

AI7

 

RX_ANALOG_INPUT

 

 

RX input

 

 

Percent

 

AI8

 

TRIP_CODE

 

 

Trip code information

None

 

Analog Output Object Instance Summary

 

 

 

 

 

 

 

 

 

 

 

 

Instance ID

Object Name

 

 

Description

 

Units

 

AO1

 

FREQ_CMD_REG

 

 

Frequency command

Hz

 

AO2

 

FM_ANALOG OUTPUT

 

 

FM output value

 

 

None

 

AO3

 

AM_ANALOG OUTPUT

 

AM output value

 

 

None

 

100