E6581268
- 25 -
3.9. Vender Specific Device Pro-files
Class code 0x64. This object provides VF-S11’s Parameter access.
All parameter’s Attribute ID is 3.
Refer to the following about each parameter’s Instance ID.
Example 1.
In case of Basic parameter “CMOd - Command mode selection”,

Communication No: 0003 -> Instance ID: 1003

Example 2.
In case of Extended parameter “F300 - PWM carrier frequency”,

Communication No: 0300 -> Instance ID: 1300

Example 3.
In case of Monitor parameter “FE03 - Output current”,

Communication No: FE03 -> Instance ID: 1E03

* Monitor parameter can access "Get" only.
3.10. About EDS-file
Even if access to each parameter of VF-S11 uses a configuration tool and an EDS file, it is
possible. As for acquisition of an EDS file, it is possible to download from homepage of our
company.
Please use what was in agreement with the software version of usage's VF-S11.
http://www.inverter.co.jp/product/inv/vfs11/dev/
- 25E -