Examples of Instance 100/150
Stop
Instance Byte 1514131211109876543210 Hex.
1, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0x0000
Output Instance 100 3, 2 ---------------- -
1, 0 0 10010 0 0 0 0 0 0 0 0 0 0 0x4800
Input Instance 150 3, 2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0x0000
Forward running 60Hz
Instance Byte 1514131211109876543210 Hex.
1, 0 1100010000000000 0xC400
Output Instance 100 3, 2 0001011101110 0 0 0 0x1770
1, 0 0 110010 0 0 0 0 0 0 0 0 0 0x6400
Input Instance 150 3, 2 0001011101110 0 0 0 0x1770
Reverse running 60Hz
Instance Byte 1514131211109876543210 Hex.
1, 0 1100011000000000 0xC600
Output Instance 100 3, 2 0001011101110 0 0 0 0x1770
1, 0 0 1100110 0 0 0 0 0 0 0 0 0x6600
Input Instance 150 3, 2 0001011101110 0 0 0 0x1770
Preset s peed 1 with forward running (sr1)
Instance Byte 1514131211109876543210 Hex.
1, 0 10000100000000010x8401
Output Instance 100 3, 2 ---------------- -
Input Instance 150 1, 0 0 110010 0 0 0 0 0 0 0 0 0 0x6400
(sr1 is set 5Hz.) 3, 2 0 0 0 0 0 0 0 11111010 0 0x01F4
Fault reset ***
Instance Byte 1514131211109876543210 Hex.
1, 0 0 0 10 0 0 0 0 0 0 0 0 0 0 0 0 0x2000
Output Instance 100 3, 2 ---------------- -
About the other command, refer to the Communications Function Instruction Manual (E6581222) section 8.1.
*** Fault reset works only 1 time when 0 -> 1.