E6581268 ①
2.4. VF-S11 communication parameters
In a network,
The supported parameters for each drive and their allowable adjustment ranges are defined in the appropriate Electronic Data Sheet (EDS) files. EDS files can be downloaded via the internet from
http://www.inverter.co.jp/product/inv/vfs11/dev/
Parameter | Function | Adjustment range | Shipment |
f800 | RJ45 | 0: 1200bps | 3 |
| Communication | 1: 2400bps |
|
| speed | 2: 4800bps |
|
|
| 3: 9600bps |
|
|
| 4: 19200bps |
|
f803 | Communication | 0: Disabled | 0 |
| error trip time | 1- 100 (s) |
|
f890 | MAC ID | 0 - 63 | 0 |
f891 | DeviceNet | 0: 125kbps | 0 |
| Communication | 1: 250kbps |
|
| speed | 2: 500kbps |
|
f892 | Communications | 0: Stop, Communication release | 0 |
| Loss action | 1: No action |
|
| (Network wire breaks) | 2: Deceleration stop |
|
|
| 3: Coast stop |
|
|
| 4: Emergency stop |
|
|
| 5: Preset speed command |
|
|
| (Preset speed by f893 setting) |
|
f893 | Preset speed No. | 0: No action | 0 |
|
|
| |
f894 | Assembly | 0: Instance 20/70 | 0 |
| Object | 1: Instance 21/71 |
|
|
| 2: Instance 100/150 |
|
|
| 3: Instance 101/151 |
|
*1 Parameter f800 is
*2 For safty, set the communication error trip time (f803).
*3 When out of range values are set up, the MS (Module Status) LED and will flash green continuously to indicate an invalid
*4 When the parameters are changed, the power must be cycled to the
- 6 -