3.7. Control Supervisor Object

Class code 0x29. This object models all the management functions for devices within the DeviceNet “Hierarchy of Motor Control Devices”. The behavior of motor control devices is described by the State Transition Diagram.

3.7.1. Control Supervisor Object Class Attributes

Attribute

Name

Data

Access

Description

Default

ID

Type

Rules

Value

 

 

1

Revision

UINT

Get

Revision of this object

1

 

 

 

 

 

Maximum instance number of an object

 

 

2

Max instance

UINT

Get

currently created in this class level of

1

 

 

 

 

 

the device

 

 

3.7.2. Control Supervisor Object Instance Attributes

 

 

 

Attribute

Name

Data

Access

 

Description

Default

ID

Type

Rules

 

Value

 

 

 

1

Number of Attributes

USINT

Get

Number of Attributes supported

13

2

Attribute List

USINT

Get

List of attributes supported

-

(ARRAY)

 

 

 

See Run/Stop Event Matrix

 

 

 

 

 

 

3

Run 1

BOOL

Get/Set

00 = Stop

-

 

 

 

 

01 = Run

 

 

 

 

 

See Run/Stop Event Matrix

 

4

Run 2

BOOL

Get/Set

00 = Stop

-

 

 

 

 

01 = Run

 

 

 

 

 

Requests Run/Stop control to be local

 

 

 

 

 

or from network.

 

 

 

 

 

0

= Local Control

 

5

Net Control

BOOL

Get/Set

1 = Network Control

-

 

 

 

 

Note that the actual status of Run/Stop

 

 

 

 

 

control is reflected in attribute 15,

 

 

 

 

 

CtrlFromNet.

 

 

 

 

 

0

= Vendor Specific

 

 

 

 

 

1

= Startup

 

 

 

 

 

2

= Not_Ready

 

6

State

USINT

Get

3

= Ready

-

4

= Enabled

 

 

 

 

 

 

 

 

 

5

= Stopping

 

 

 

 

 

6

= Fault_Stop

 

 

 

 

 

7

= Faulted

 

 

 

 

 

1

= (Enabled and Run1) or

 

7

Running 1

BOOL

Get

 

(Stopping and Running1) or

-

 

(Fault_Stop and Running1)

 

 

 

 

 

 

 

 

 

 

0

= Other state

 

 

 

 

 

1

= (Enabled and Run2) or

 

8

Running 2

BOOL

Get

 

(Stopping and Running2) or

-

 

(Fault_Stop and Running2)

 

 

 

 

 

 

 

 

 

 

0

= Other state

 

9

Ready

BOOL

Get

1

= Ready or Enabled or Stopping

-

0

= Other state

 

 

 

 

 

10

Faulted

BOOL

Get

1

= Fault Occurred (latched)

-

0

= No Faults present

 

 

 

 

 

11

Warning

BOOL

Get

1

= Warning (not latched)

-

0

= No Warnings present

 

 

 

 

 

12

Fault Reset

BOOL

Get/Set

0->1 = Fault Reset

-

0

= No action

 

 

 

 

 

 

 

 

 

Status of Run/Stop control sourse.

 

15

Control From Net

USINT

Get

0 = Control is local

-

 

 

 

 

1

= Control is from network

 

- 22 -

Page 23
Image 23
Toshiba DEV001Z manual Control Supervisor Object Class Attributes, Control Supervisor Object Instance Attributes