Toshiba G8000 Series Recommended Cable Size and Tightening Torque for 180kVA UPS

Models: G8000 Series

1 41
Download 41 pages 8 Kb
Page 31
Image 31

Table 11.4 Recommended Cable Size and Tightening Torque for 180kVA UPS.

Block Number

Cable Size

Tightening Torque

 

 

 

1

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

2

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

3

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

4

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

5

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

6

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

7

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

8

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

9

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

10

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

11

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

*12

Two 4/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

*13

Two 4/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

NOTE: Maximum cable size is 350MCM.

*Two battery strings or more (consult factory if using one battery string).

Table 11.5 Recommended Cable Size and Tightening Torque for 225kVA UPS.

 

Block Number

Cable Size

Tightening Torque

 

 

 

 

 

1

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

 

 

2

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

3

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

4

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

5

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

6

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

7

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

8

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

9

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

10

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

11

Two 2/0 or larger

5.8 kg-m (500 in-lbs)

 

*12

Two 4/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

 

 

*13

Two 4/0 or larger

5.8 kg-m (500 in-lbs)

 

 

 

 

NOTE: Maximum cable size is 350MCM.

*Two battery strings or more (consult factory if using one battery string).

30

Page 31
Image 31
Toshiba G8000 Series installation manual Recommended Cable Size and Tightening Torque for 180kVA UPS