Toshiba G8000 Series installation manual External Breakers, External Breaker Rating

Models: G8000 Series

1 41
Download 41 pages 8 Kb
Page 35
Image 35

11.3 External Breakers

The G8000 UPS units are not equipped with circuit breakers. The electrical contractor should provide the external breakers for AC input, Bypass input, DC input, and AC output. See Figure 11.1 for the position of the breakers.

Table 11.9 shows the minimum rating for each capacity of G8000 UPS breakers. The Bypass input and the AC output require 4-pole breakers.

Table 11.9 External Breaker Rating.

 

AC input / Bypass input / AC output

DC input

Capacity

Minimum Breaker Rating

Minimum Breaker Rating

 

 

 

 

100kVA

480V - 150A

500VDC – 400A

 

 

 

125kVA

380V - 250A

500VDC – 600A

 

 

 

150kVA

480V - 225A

500VDC – 600A

 

 

 

180kVA

380V - 350A

500VDC – 750A

 

 

 

225kVA

480V - 350A

500VDC – 900A

 

 

 

250kVA

380V - 500A

500VDC – 1100A

 

 

 

300kVA

480V - 450A

500VDC – 1,200A

 

 

 

34

Page 35
Image 35
Toshiba G8000 Series installation manual External Breakers, External Breaker Rating