Installation Environment

CAUTION

The UPS is to be installed in a controlled environment.

Improper storage and installation environment may deteriorate insulation, shorten component life and cause malfunctions.

Keep the installation environment per standard described in Table

5.1.

MANDATORY

 

 

Table 5.1 - UPS Installation Environment Standard

 

 

 

 

 

No.

Item

 

Environment standard

 

 

 

 

 

1

Installation location

Indoors

 

 

 

 

 

 

2

Ambient

Minimum temperature: 0°C, Maximum temperature: 40°C The average temperature

temperature

over any 24-hour period must be in the range 5 to 35°C.

 

 

 

 

 

3

Relative humidity

The relative humidity must be held between 30 and 90%. There must be no

condensation due to temperature changes.

 

 

 

 

 

 

4

Altitude

This equipment must not be applied at altitudes that exceed 1000m (3240 ft) above

seal level.

 

 

 

 

 

 

 

 

 

 

 

 

Vibrations in the installation environment must have frequencies either lower than

 

 

10 Hz, or higher than 20 Hz.

 

 

 

 

For vibrations under 10 Hz, the acceleration due to those vibrations must not

5

Vibration and

exceed 0.5 G.

 

 

 

 

 

mechanical shock

For vibrations over 20 Hz and under 50 Hz, the acceleration due to those vibrations

 

 

 

must not exceed 0.5 G.

 

 

 

 

For vibrations over 50 Hz and under 100 Hz, the total amplitude must not exceed

 

 

0.1 mm.

 

 

 

 

 

 

 

 

Dust in the room where the UPS is installed must not exceed normal atmospheric

6

Dust

dust levels. In particular, that dust must not include iron particles, oils or fats, or

 

 

organic materials such as silicone.

 

 

 

 

7

Flammable gas

There should be no flammable/explosive gas.

 

 

 

 

 

 

 

Hydrogen sulfide (H2S)

 

No more than 0.0001 PPM

 

 

 

 

 

 

 

Sulfurous acid gas (SO2)

 

No more than 0.05 PPM

 

 

 

 

 

 

 

Chlorine gas (Cl2)

 

No more than 0.002 PPM

 

 

 

 

 

 

 

Ammonia gas (NH3)

 

No more than 0.1 PPM

 

 

 

 

 

 

 

Nitrous acid gas (NO2)

 

No more than 0.02 PPM

 

 

 

 

 

 

 

Nitrous oxides (NOx)

 

No more than 0.02 PPM

 

 

 

 

 

 

 

Ozone (O3)

 

No more than 0.002 PPM

 

 

 

 

 

 

 

Hydrochloric acid mist (HCl)

 

No more than 0.1 mg/m3

 

 

 

 

 

9

Page 10
Image 10
Toshiba G8000 Series installation manual UPS Installation Environment Standard