Toshiba G8000 Series installation manual Grounding configuration

Models: G8000 Series

1 41
Download 41 pages 8 Kb
Page 38
Image 38

11.6 Grounding configuration

This section describes the grounding configuration with AC input service entrance.

As inadequate grounding configuration causes problems on start-up, connections for the ground line and the neutral line must be done properly according to the system configuration.

11.6.1 Recommended configuration with input neutral grounded

Figure 11.8 shows recommended grounding configuration with input neutral grounded.

The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should be open, as the neutral line must be grounded only at one point in a system. And the neutral line must be properly fed to the bypass input.

Input Source

3

N

3

G

 

< UPS Cabinet >

3

 

N

 

3

3

 

 

N

G

G

3

 

 

 

 

 

N

 

 

To the

 

 

 

 

 

G

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disconnect

The Cable

Figure 11.8 - Grounding configuration with input neutral grounded.

A jumper cable of 2AWG (or 38mm2) is provided between the neutral terminal and ground bus in the UPS cabinet. Notice that the electrical contractor should unscrew and disconnect the jumper cable in this configuration. The cable location is illustrated below.

 

< 100~225kVA >

 

Ground

Neutral

 

Terminal

 

Bus

 

Disconnect

 

 

 

 

 

 

 

 

Jumper

 

 

 

Cable here

< 250/300kVA >

Neutral

Terminal

Ground

Bus

Disconnect

Jumper

Cable here

Figure 11.9 - Jumper cable between the neutral terminal & ground bus.

37

Page 38
Image 38
Toshiba G8000 Series installation manual Grounding configuration, Recommended configuration with input neutral grounded