Heating System
Electric heating option
All electric heat models shall be completely assembled and have wired electric heating system integral within the rooftop unit. Heavy duty nickel chromium elements internally wired with a maximum density of 40 watts per square inch shall be provided. Heater circuits shall be 48 amps or less, each individually fused. Automatic reset high limit control shall operate through heater backup contactors.The 460 and 575 volt electric units shall have optional factory mounted non-fused disconnect switch located in the main control panel to serve the entire unit.The 200 and 230 volt SEHF models shall have separate power supply to heating section. All voltages of the SEHG models shall have single power supply to serve the entire unit.
Steam heating option
Steam coils shall beType NS, with non- freeze steam distribution circuits. Distributor tubes shall be located concentrically within condensing tubes to assure even steam distribution. Coils shall be pitched to provide complete drainage. Steam modulating valve with actuator shall be provided.
Hot water heating option
Hot water coils shall beType W and factory mounted in the rooftop unit to provide complete drainage of coil. Hot water modulating valve with actuator shall be provided.
Gas-fired heating option
All gas-fired units shall be completely assembled and have a wired gas fired heating system integral within unit. Units shall be UL or CSA approved specifically for outdoor applications downstream from refrigerant cooling coils. All gas piping shall be threaded connection with a pipe cap provided. Gas supply connection shall be provided through the side or bottom of unit. All units shall be fire tested prior to shipment.
•Heat Exchanger shall be tubular two pass design with 16-gauge stainless steel primary and 18-gauge stainless
steel secondary heat exchanger surfaces. Free floating design shall eliminate expansion and contraction stresses and noises. Gasketed cleanout plate shall be provided for cleaning of tubes/turbulators. Heat exchanger shall be factory pressure and leak tested.
•Burner shall be industrial type burner with a air proving switch to prevent burner operation if burner is open for maintenance or inspection. Ceramic cone shall be provided to shape the flame to prevent impingement on sides of heat exchanger drum. Burner assembly shall house ignition and monitoring electrode.
•Combustion Blower shall be centrifugal type fan to provide air required for combustion. Fan motor shall have built-in thermal overload protection.
•Gas Safety Controls shall include electronic flame safety controls to require proving of combustion air prior to ignition sequence which shall include a 60 second pre-purge cycle. Direct spark ignition shall be provided on 235 and 350 MBh heat exchangers and pilot ignition shall be provided on 500, 850 and 1000 MBh heat exchanger units. Sixty second delay shall be provided between first and second stage gas valve operation on two-stage heaters. Continuous electronic flame supervision shall be provided as standard.
•Full Modulation Gas Heaters shall be made from grades of stainless steel suitable for condensing situations. The heater shall have a turn down ratio of at least 4 to 1.
•Limited Modulation Gas Heaters shall have a minimum turn down ratio of at least 3 to 1.
Accessories
Roof Mounting Curb
Roof mounting curb shall be fourteen gauge zinc coated steel with nominal two-inch by four-inch nailer setup.
Supply/return air opening gasketing shall be provided. Curb shall ship knocked down for easy assembly.
Channel shall be provided to allow for adjustment of return air opening location. Curb shall be manufactured to National Roofing Contractors Association guidelines.
Electronic Zone Sensors
•Zone Sensors shall provide two temperature setpoint levers, Heat, Auto, Off, or Cool system switch, Fan Auto or Fan On switch. Optional status indication LED lights, System On, Heat, Cool, and Service shall be available.These sensors shall be used with CV units.
•Programmable Night Setback Sensors shall be electronic programmable sensors with auto or manual changeover with 7 day programming. Keyboard shall provide selection of Heat, Cool, Fan Auto or On. All programmable sensors shall have System On, Heat, Cool, Service LED/ indicators as standard. Night setback sensors shall have (1) Occupied,
(1) Unoccupied and (2) Override programs per day. Sensors shall be available for CV zone temperature control and VAV Supply Air temperature control.
•VAV zone sensor shall be provided with supply air single temperature setpoint and AUTO/OFF system switch. Status indication LED lights shall include: System On, Heat, Cool and Service. Sensor shall be provided for zone temperature control with VAV units.
•Remote Sensor shall be available to be used for remote zone temperature sensing capabilities when zone sensors are used as Remote panels.
•Fast Warm-Up Sensor shall be used as Morning warm-up sensor with VAV units.
•Integrated Comfort™ System sensors shall be available with sensor only, sensor with timed override, and sensor with local temperature setpoint adjustment with timed override.
•Remote Minimum Position Potentiometer shall be available to remotely adjust the minimum position setting of the unit’s economizer.