Trane RT-PRC010-EN manual Application Considerations, High Capacity Evaporator Coil

Models: RT-PRC010-EN

1 104
Download 104 pages 11.81 Kb
Page 13
Image 13
High Capacity Evaporator Coil

Application Considerations

High Capacity Evaporator Coil

Rooftops are popular because of their “packaged” nature. Everything needed is contained in one box; mix-matching is neither necessary nor available. With this convenience comes some disadvantages; one is the rooftop’s cooling capacity may not exactly match the building load. It is conceivable that a 50 ton rooftop would need to be used on an application that is 41 tons, simply because the 40 ton rooftop does not meet capacity.

In order to avoid such occurrences, and to more closely match the rooftop’s capacity to the building load, a high capacity evaporator coil option is available on all IntelliPak® Rooftops 20 to 105 tons.These high capacity coils have an increased number of evaporator coil rows as compared to standard and enhanced evaporator tube surfaces, resulting in a higher capacity. Capacity tables for both standard and high capacity coils are available in the cooling data section of this catalog. SeeTable PD-43 for the pressure drops associated with the high capacity coil option.This pressure drop should be added to the total static pressure used to size the supply fan motor.

Low Ambient Operation — Human Interface Recommendations

Who wants to be on a roof at sub-zero temperatures? We can understand a service technician’s reluctance to do this; that’s why we recommend using a remote mounted Human Interface Panel. The service technician can troubleshoot and diagnose in the comfort of a mechanical room.

Corrosive Atmospheres

Trane’s IntelliPak® Rooftops are designed and built to industrial standards and will perform to those standards for an extended period

depending on the hours of use, the quality of maintenance performed, and the regularity of that maintenance. One factor that can have an adverse effect on unit life is its operation in a corrosive environment.

When rooftops are operated in corrosive environments,Trane recommends that copper fins be utilized on the condenser and/or evaporator coil. Because copper is more resistant to corrosion than aluminum, coil life expectancy is greatly increased. Some industry applications expose equipment to corrosive agents that even copper cannot fully resist. For those special applications, a baked phenolic resin coating (i.e. Heresite) is highly desirable. Baked phenolic coatings or copper fins on the condenser and/or evaporator coils are available on Trane’s IntelliPak Rooftops.

Ventilation Override Sequences

One of the benefits of using an exhaust fan rather than a return fan, in addition to the benefits of lower energy usage and improved building pressurization control, is that the rooftop can be used as part of a ventilation override system. Several types of sequences can be easily done when exhaust fans are a part of the rooftop system.

What would initiate the ventilation override control sequence?Typically, a manual switch is used and located near the fire protection control panel.This enables the fire department access to the control for use during or after a fire. It is also possible to initiate the sequence from a field-installed automatic smoke detector. In either case, a contact closure begins the ventilation override control sequence. CAUTION!: The ventilation override system should not be used to signal the presence of smoke caused by a fire.

Trane can provide five (5) different ventilation override sequences on both

CV and VAV IntelliPak® Rooftops. For your convenience the sequences can be factory preset or fully field editable from the Human Interface Panel orTracer®. Any or all five sequences may be “locked” in by the user at the Human Interface Panel.

The user can customize up to five (5) different override sequences for purposes such as smoke control.The following parameters within the unit can be defined for each of the five sequences:

Supply Fan — on/off

Inlet GuideVanes — open/closed/ controlling

Variable Frequency Drives — on (60 Hz)/off (0 Hz)/controlling

Exhaust Fan — on/off

Exhaust Dampers — open/closed

Economizer dampers — open/closed

Heat — off/controlling (output for)VAV Boxes — open/controlling

Compressors and condenser fans are shut down for anyVentilation Override sequence. Factory preset sequences include unit Off, Exhaust, Purge, Purge with duct pressure control, and Pressurization. Any of the user-defined Ventilation Override sequences can be initiated by closing a field supplied switch or contacts connected to an input on the Ventilation Override Module. If more than one ventilation override sequence is being requested, the sequence with the highest priority is initiated. Refer to the Sequence of Operation provided in the Control section of this catalog for more details on each override sequence.

Natural Gas Heating Considerations

The IntelliPak standard, or limited modulation, gas heat exchangers are not recommended for applications with mixed air conditions entering the heat exchanger below 50°F. Mixed air temperatures below 50°F can cause condensation to form on the heat

RT-PRC010-EN

13

Page 13
Image 13
Trane RT-PRC010-EN Application Considerations, High Capacity Evaporator Coil, Corrosive Atmospheres, •Supply Fan — on/off